San Joaquin County
<br /> Environmental Health Department
<br /> 1868 East Hazelton Avenue, Stockton, California 95205-6232
<br /> Telephone: (209)468-3420 Fax: (209)468-3433 Web:www.sjgov.org/ehd
<br /> erground Storage Tank Progra ion Report
<br /> Facility Name: Facility Address: Date:
<br /> GRANT LINE SHELL* 2375 W GRANT LINE RD TRACY May 15 2018
<br /> SUMMARY OF
<br /> VIOL
<br /> OIONS
<br /> (CLASS.1,CLASS ll;or MINOR Notice to Comply)
<br /> Item# Remarks
<br /> 301 HSC 25292.1 UST system is not operated to prevent unauthorized release, including spills and overfills.
<br /> The fuel filters under the dispensers are not located to allow drips and leaks to drain back into the UDC. The
<br /> underground storage tank system shall be operated to prevent unauthorized releases. Immediately provide approved
<br /> secondary containment for the filters under permit and inspection by the EHD.
<br /> This is a Class II violation.
<br /> 314 HSC 25290.1, 25290.2, 25291 Failed to have secondary containment or secondary containment not tight.
<br /> The fuel filters under the dispensers are not located to allow drips and leaks to drain back into the UDC. Secondary
<br /> containment shall be provided for all single-walled UST components. Immediately provide approved secondary
<br /> containment for the filters under permit and inspection by the EHD.
<br /> The April 12, 2017 secondary containment test results indicate failures of the following componenets:
<br /> STP sumps: 8713,89A,89B,91 A, 91 B, diesel
<br /> Piping: 87B,89A, 89B,91 A,91 B, dieesl
<br /> UDCs: 1/2, 3/4, 9/10, 15/16, 17/18, 19/20, 21/22
<br /> A permit for UDC and piping repairs was approved on 11/29/17. No inspections have been scheduled. Work was
<br /> observed in progress on the UDCs while on site. No passing test results have been received for these components.
<br /> All secondary containment for the UST system must be tight. Immediately have a properly licensed, trained, and
<br /> certified contractor repair or replace the failed component under permit and inspect of the EHD.
<br /> This is a repeat violation, Class II.
<br /> Overall Inspection Comments:
<br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement
<br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting
<br /> paperwork, by June 14, 2018
<br /> Please be aware that as of January 1, 2014, facility operators are required to upload the following UST program
<br /> documents into the California Environmental Reporting System (CERS): UST Monitoring Site Plan, UST
<br /> Certification of Financial Responsibility, UST Response Plan, UST Letter from Chief Financial Officer (if
<br /> applicable), and the Owner Statement of Designated Operator Compliance. The UST Owner/Operator: Written
<br /> Agreement, if applicable, can be stored at the facility or uploaded into CERS.
<br /> Note: When they fail, the 87, 89, and diesel spill buckets shall be replaced with a spill bucket that has a minimum
<br /> capacity of 5 gallons, is protected from galvanic corrosion, and has either a drain valve which allows drainage of
<br /> the collected spill into the primary container or provides a means to keep the spill container empty pursuant to
<br /> CCR, Title 23, section 2635(b)(1).
<br /> Note: Sensor testing, sensor out, power out, positive shutdown, and sensor set up were conducted by the
<br /> technician while on site, but were not observed. The ball floats were unable to be verified on site because the
<br /> caps won't open.
<br /> FA0003772 PR0232469 SCO01 05/15/2018
<br /> EHD 23-01 Rev.09/22/16 Page 5 of 6 Underground Storage Tank Program OR
<br />
|