Laserfiche WebLink
0 RECEIVED <br />SWRCB, January 2002 g <br />4. TANK ANNULAR TESTING ENVIRONMENTAL <br />Test Method Developed By: X Tank Manufacturer Industry Standard I Professional ngmeer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure X Vacuum C Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Gast Vacuum Pump/Vacuum Gauge in Hg. Equipment Resolution: - ''/2" x -30" Hg. <br />Is Tank Exempt From Testing?' <br />ESEEM 11 <br />Tank # 1 Tank # 2 Tank # Tank # <br />No No <br />Tank Capacity: <br />6K 6K <br />Tank Material: <br />Jacketed DW Steel Jacketed DW Steel <br />Tank Manufacturer: <br />Trusco Trusco <br />Product Stored: <br />Diesel Regular 87 <br />Wait time between applying <br />vacuum and starting test: <br />10 Minutes 10 Minutes <br />Test Start Time: <br />9:50 9:50 <br />Initial Reading (RI): <br />-10 Hg. -10 Hg. <br />Test End Time: <br />10:50 10:50 <br />Final Reading (RF): <br />-10 Hg. -10 Hg. <br />Test Duration: <br />1 Hour 1 Hour <br />Change in Reading (RF -R,): <br />0 Hg. 0 Hg. <br />Pass/Fail Threshold or Criteria: <br />No Loss in Hg. No Loss in Hg. <br />Test Result: <br />Pass Pass <br />Was sensor removed for testing? <br />Yes Yes <br />Was sensor properly replaced and <br />verified functional after testing? <br />Yes Yes <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. {California Code of Regulations, Title 23, Section 2637(a)(6)} <br />