SAN JOAQUIN COUNTY <br /> ENVIRONMENTAL HEALTH DEPARTMENT frill <br /> 1868 East Hazelton Avenue, Stockton, California 95205-6232 / <br /> Telephone:(209)468-3420 Fax:(209)468-3433 Web:www.sjgov.org/ehd rLel� <br /> UNDERGROUND STORAGE TANK(UST) PROGRAM INSPECTION REPORT CONTINUED <br /> Facility Flying J Travel Plaza Facility 1501 N. Jack Tone Road, Ripon Inspection 5/16/2014 <br /> Name: y g Address: p Date: <br /> VIOLATIONS <br /> # C1 C2 M Code Section HSC=CA Health and Safety Code;CFR=Code of Federal Regulations <br /> C1=Class 1 violation;C2=Class 2 violation;M=Minor violation <br /> 702 CCR 2643(e) Biennial tightness test of gravity piping not performed(pre-January 1,1984) (M7) <br /> 703 CCR 2643(d) Triennial line test for conventional suction piping not performed(pre-January 1, 1984) (M1) <br /> 999 Other: See attached"Continuation—Official Inspection Report"for violation(s)not listed above. <br /> SUMMARY OF VIOLATIONS <br /> CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> This is a follow up re-inspection to observe re-testing of the two spill buckets that had failed on May 14, <br /> 2014 during Monitoring System Certification. This report does not supersede the May 14, 2014 MSC <br /> and Routine inspection report, where all the violations on the report with the exception of Violation #313 <br /> remains in effect. <br /> 313 (Repeat). The diesel UST (Tank 5 and Tank 4) spill containers failed when tested on May 14, 2014 . <br /> All spill containers shall have a minimum capacity of five gallons and be capable of containing a spill or <br /> overfill until it is detected or cleaned up. Immediately discontinue deposition of petroleum into this tank <br /> until the component is repaired or replaced by a properly licensed, trained, and certified contractor under <br /> permit and inspection of the EHD. The spill container components (drain valve, cap) had been cleaned <br /> up and retested during the inspection today, and they passed. This violation has been corrected. <br /> ALL EHD STAFF TIME ASSOCIATED WITH FAILING TO COMPLY BY THE ABOVE NOTED DATES WILL BE BILLED AT THE CURRENT HOURLY RATE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Inspector: Received By: Title: <br /> EHD 2 2 Re b4/ /12 Page 3 UST INSPECTION REPORT <br />