i,. <br /> qq�� <br /> SWRCB,January 2002 Page 3 of 3 <br /> 7. UNDER-DISPENSER CONTAINMENT !2Q,.TESTING <br /> Test Method Developed By: ❑UDC Manufacturer A Indu � Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum 9 Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: INCON TS-STS Equipment Resolution: +/-0.002" <br /> mmmmmmmmmmommm <br /> UDC# 22 Satellite UDC# UDC# UDC# <br /> 7Heigght <br /> Manufacturer: Unknown <br /> Material: Fiber lass <br /> De the 30" <br /> from UDC Bottom to Top 13" <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 91, <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to D <br /> testing: <br /> Dry <br /> Portion of UDC Tested' 17" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both []Yes ❑No X NA ❑Yes []No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> product and water)?` <br /> Turbine shutdown response time N/A <br /> Is system programmed for fail- ❑Yes []No X NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> safe shutdown?* <br /> Was fail-safe verified to be ❑Yes ❑No 9NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and 15min <br /> starting test <br /> Test Start Time: 11:24am <br /> Initial Reading(RI): 4.8172" <br /> Test End Time: 11:39am <br /> Final Reading(RF): 4.8158" <br /> Test Duration: 15min <br /> Change in Reading RF-RI): 0.0014" <br /> Pass/Fail Threshold or Criteria: +/-0.002" <br /> Test Result: ® Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fail <br /> Was sensor removed for teAand <br /> ®Yes []No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> Was sensor properly replacverified functional after tesW Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Disp. #22 Satellite had failed previously. Repairs made were replacing all 3 Electrical & 1 product line penetration. Disp. <br /> #22 Satellite UDC is now passing hydrostatic testing. <br /> ' If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />