Laserfiche WebLink
• <br />01 <br />AlitechPetrB <br />Compliance without Compromise <br />REC,FtED <br />P.O. Box 4208 <br />Sonora CA 95370 <br />m 6 7 2017 Phone: 209-532-7320 <br />Fax: 209-533-2650 <br />ENVIRONMENTAL HEALTH mail@alltechpetro.com <br />nFPARTMENT www.alltechpetro.com <br />PRECISION TEST DATA SHEET for PIPING <br />Facility: Flying J #618 Ripon <br />Address: 1501 Jack Tone Rd. <br />City: Ripon, CA 95366 <br />Facility contact: Steve Sills <br />L.I.A.: Elena Manzo <br />Date: 3/7/17 <br />Phone: 909-730-9185 <br />L.I.A. Phone: 209-468-3440 <br />Hasstech Accu -Rite Pressurized Pinina Tester <br />Product <br />T1 <br />Diesel/ <br />Bio <br />T2 <br />Diesel/ <br />Bio <br />Turbine isolation method <br />* <br />Ball <br />Valve <br />Ball <br />Valve <br />Day tank isolation <br />method <br />Ball <br />Valve <br />Ball <br />Valve <br />Test pressure, PSI <br />60 <br />60 <br />Initial cylinder level <br />0.0725 <br />0.0725 <br />Final cylinder level <br />0.0650 <br />0.0650 <br />Time Started <br />9:50 <br />9:50 <br />Time Completed <br />10:50 <br />10:50 <br />Total test time, minutes <br />60 <br />60 <br />Result: Volume change in <br />GPH <br />0.0075 <br />0.0075 <br />Conclusion: *Pass/ <br />Fail <br />Pass <br />Pass <br />Leak Detector Test: <br />NJ <br />N/T <br />* Pass/Fail threshold is 0.0100 GPH per Manufacturer's protocol. <br />Hasstech Certification # 3453 LTN Expiration: 2/24/18 <br />Remarks: <br />Test technician: 00i <br />Chad White <br />