Laserfiche WebLink
I <br /> Veeder-Root Sensor Application Guide <br /> Piping Sump Sensor <br /> The Piping Sump Sensor is installed in a tank piping sump and will detect the presence of a liquid.An open sensor <br /> triggers a Sensor Out alarm. <br /> i <br /> Table 5. Piping Sump Sensor Features and Console Compatibility <br /> I <br /> Item Description <br /> i <br /> Form numbers 794380-208 <br /> Operating principle Float/magnetic reed switch <br /> Product activation height2 Gasoline-1.84 inch(4.67cm) <br /> Operating temperature 0 to+140oF(0 to+60°C) <br /> i <br /> Dimensions 12"(30.5cm)high,l.9"(4.8cm)diameter <br /> Compatible consoles TLS-450/8600 Series,TLS4/8601 Series,TLS-350 Series,TLS-300 Series <br /> Console Interface TLS-300 Series-No input module required <br /> Module <br /> TLS-350 Series,Interstitial/Liquid Sensor Interface Module,8 sensor input,P/N 329358-001 <br /> TLS-450/8600 Series-Universal Sensor Module(USM),16 sensor input,P/N 332812-001 <br /> TLS4/8601 Series-Universal Sensor Input Output Module(USIOM)(AC ver.),12 sensor input,P/N 333238-001;(AC ver.), <br /> 6 sensor input,P/N 333238.002;(DC ver.),12 sensor input,P/N 333238-003;(DC vee),6 sensor input,P/N 333238-004 <br /> Maximum number of TLS-300 Series(8) <br /> sensors monitored per <br /> console TLS-350 Series,(48) <br /> TLS-450/8600 Series(32) <br /> TLS4/8601 Series(12) <br /> Compatible fuels 10096 Gasoline; Diesel;Bio-Diesel;Kerosene;Jet fuel;Aviation Gas;Waste Oil/Used Oil;and 8596 Ethanol/1546 Gasoline; <br /> Motor Oil <br /> 1Sensors 794380-208 and-209 are direct replacements for sump sensor 794380-206 <br /> ZFor additional third party evaluation data see:http://nwglde.org/evals/veeder_root_m.html <br /> i <br /> Miscellaneous <br /> • Installation kit 330020-076 A ••To Existing conduit <br /> I FLEXIBLE(see Fig.3) •' or piping <br /> • Standard cable length: 12 feet <br /> (3.66m) - Product <br /> Cable to junction boxke Cable to junction pipe <br /> and seal-off box and seal-off ., <br /> a <br /> *Sump sensor should: ; 1 <br /> 1.Hest on the base of the sump <br /> 2.Be positioned as close to outer \ I S <br /> wall as possible. Sump sensor* <br /> 3.Be mounted In a true vertical ; (installation examples) ' <br /> position. ti <br /> 4.Be installed only in a dry sump ;h <br /> Irv; <br /> um p base <br /> eft <br /> TiciA Example Piping Siu�rnip Sensor installation, <br /> rim d <br /> 5 <br />