Laserfiche WebLink
SEP U 9 <br /> HOW TO LOCATE THE POSITION OF THE <br /> 71SO AT 95%TANK CAPACITY i• Measuring Stick <br /> The length of the upper tube and the placement of <br /> the 71 SO valve body determine the shut-off point. <br /> Following the standard instructions for the OPW <br /> 71 SO will provide for initial shutoff at 95%. In all <br /> cases, the upper tube length must be a minimum of <br /> 6-1/2" plus the length of the riser pipe. All length <br /> measurements are in inches. Riser Pipe <br /> INSTRUCTIONS with Face (A) <br /> Seal Adaptor To Tank <br /> (B) <br /> 1.) Find tank capacity(in gallons)from tank Top(I-D-) To Tank <br /> calibration chart provided by tank manufacturer. Bottom <br /> 19- <br /> 2.)Calculate 95%of capacity. t' <br /> { =CT �1 (�1/`� 6-1/2„ <br /> 3.) Locate the 95%volume number on the tank <br /> calibration chart. O UV- `A.VA <br /> Z Figure 1 <br /> 4.) Find the dipstick number(X)which corresponds <br /> to the 95%tank volume. And, find the dipstick <br /> number(Y)which corresponds to the EXAMPLE <br /> 100%volume. 1.) For an Owens-Corning Model G-3 Fiberglass® <br /> Tank Calibration Chart: <br /> 5.) Subtract the dipstick number(X)from the tank Tank Capacity- 10,000 gal., nominal 9,403 gal. <br /> diameter(Y)to find the upper tube reference NOTE: Use actual capacity only <br /> number(Z). -1 t'_-M'z I_t <br /> (Y) -(X) = (Z) 2.)95%of actual tank capacity= 0.95 x <br /> 6.) Subtract 2"from (Z)to find the upper tube depth 9403 gal. = 8933 gal. <br /> (C)_ 3.)The closest number which is less than 8933 gal. <br /> (Z)-2"= C Is 8910 gal. Choosing the closest number less <br /> than 95% of actual capacity ensures that the <br /> 7.) Is C less than 6-1/2"? initial shutoff will occur when the tank is no more <br /> than 95%full. <br /> NO Upper tube length is C plus the distance <br /> from the top of the Face Seal Adaptor 4.)The calibration chart reading of 8910 gal. \ <br /> installed on the riser pipe to the inside, top corresponds to a dipstick measurement o 82". <br /> lip of the storage(A). <br /> Length -C + A 5.) Dipstick number(X) =82" <br /> Upper Tube Len <br /> g - ( ) Tank diameter(Y) =92" <br /> YES Upper tube length is 6-1/2" plus the riser (Y) - ((Z) = 10 10 - (Z) (92 "-82" = 10") <br /> pipe measurement(A). <br /> 7.) (Z)-2"=C (10"-2" = 8") <br /> Upper Tube Length = 6-1/2" + (A) C= 811 <br /> NOTE: You must find the actual tank capacity 7.) Is 8" less than 6-1/2"? <br /> number that correlates to the 6-1/2" +(A)depth <br /> for the station records. This number may also NO Measure the distance from the top of the <br /> be used for the purposes of calibrating an FSA-400 Face Seal Adaptor installed on the <br /> electronic tank level system. riser pipe to the inside, top lip of the storage <br /> tank and obtain measurement(A). <br /> ®Registered T.M.-Owens Corning Fiberglass Corporation Upper tube length = C+ (A) <br /> 64 <br />