Laserfiche WebLink
REDJACKET. ® CPT Controller Manual <br /> yellow LED is flashing, a soft fault has occurred. (See "Soft Faults" <br /> and "Signals and Alarms" below.) <br /> Red LED. The red LED on the cover indicates hard fault <br /> occurrences. If the red LED is off, no fault has occurred. If the red <br /> LED is flashing, a hard fault has occurred. (See "Hard Faults" and <br /> "Signals and Alarms"below.) <br /> Red Capacitor Charge Light. The red LED on the Inverter board <br /> indicates hazardous voltage on the capacitor bank. Personal injury <br /> can occur if service is performed while the power is on. <br /> Voltage stored in the capacitor bank of the CPT <br /> Controller presents a risk of potentially lethal electrical <br /> shock EVEN AFTER THE POWER IS DISCONNECTED. <br /> After disconnecting the power,wait about 2-5 minutes, <br /> and until the red Capacitor Charge Light goes out, <br /> before servicing or removing the controller. <br /> f <br /> Y <br /> Chapter 5:Service and Repair 5-2 ARE260-240 Rev.A ♦ 6/97 <br />