Laserfiche WebLink
Jerry Yoshioka. <br /> San Joaquin County <br /> Environmental Health Division -2- July 31, 1997 <br /> 6. The model number for the Veeder Root Interstitial Sensor Interface Module is VR 329356-002 <br /> (see revised Sheet TK4-3) <br /> 7. The dual fill ports for the 20,000-gallon tank are equipped with 5-gallon overfill/spill containers <br /> on both the fill and Stage I vapor recovery risers as shown on Sheet TK2-1B. Each fill location <br /> is equipped with an overfill prevention drop tube as specified on Sheet TK4-3. Ball float valves <br /> are located on the opposite side of the tank(turbine side) where the vent and Stage II vapor <br /> recovery headers enter the tank, as shown on Sheets TK2-lA and TK2-1B. <br /> 8. Siphon lines(active and future)are double-contained as shown on Sheets TK2-lA and TK2-1B, <br /> and the details shown on Sheet TK3-2. They shall be compliance tested as pressurized piping. <br /> Res tfully, <br /> Stephen H. Kirk <br /> Design Engineer <br /> SHK/jss/ps <br /> 5951C.031 <br /> enc: As Noted <br />