Laserfiche WebLink
Installation Guide THIS SECTION IS ONLY FOR.TECHNICIANS AND INSTALLERS! <br /> DIP SWITCH S1 SETTINGS <br /> Table 15.DIP Switch S1 <br /> Switch Position <br /> 1 Serial address AO Switch 1,2 positions: Off,Off=1 <br /> (default), On,Off=2, Off, On=3,On, <br /> 2 Serial address Al On=4 <br /> NOTE: For standalone operation,settings <br /> must be OFF, OFF.Also,for multiple <br /> pumps, master must be highest address. <br /> 3 Serial baud rate: Off=9600,On=19200(default) <br /> (DO NOT CHANGE!) <br /> i <br /> 4,5,6 Reserved(DO NOT CHANGE!) <br /> 7 D3, D4 LEDs:Off=normal(default)(DO NOT <br /> CHANGE!), On=disabled <br /> 8 Serial time-out:Off=enabled(default), On= <br /> disabled <br /> THIS SECTION IS ONLY FOR TECHNICIANS AND INSTALLERS! <br /> Fault Reset Switch(S2) <br /> Pressing the Fault Reset switch will reset the Logic board only. <br /> Jog Test Switch(S3) <br /> Pressing the Jog Test switch will test power to the pump only. <br /> Power LED(Dl) <br /> The green Power LED is on while power is applied to the unit. <br /> Run LED (D3) <br /> When the red Run LED is flashing slowly the motor has stopped.When the LED is flashing fast the motor is <br /> running. <br /> Fault LED(D4) <br /> The number of red Fault LED flashes indicate what type of problem has occurred on the Logic board.This <br /> LED is to assist technicians in Logic board diagnostics. <br /> 24 <br />