Laserfiche WebLink
Monitoring System Certification <br /> D. Results of Testing/Servicing <br /> Software version installed: 16.02 <br /> Complete the following checklist: <br /> 0 yes ❑ No* is the audible alarm operational? <br /> N Yes ❑ No* Is the visual alarm operational? <br /> g Yes ❑ No* I Were all sensors visually inspected,functionally tested,and confirmed operational? <br /> 0 Yes ❑ No* Were all sensors hustalled at lowest point of secondary containment and positioned so that other equipment will <br /> not interfere with their proper operation? <br /> ❑ Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) <br /> 0 N/A Operational? <br /> C9 Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment <br /> ❑ N/A monitoring system detects a leak,fails to operate,or is electrically disconnected? If yes:which sensors initiate <br /> positive shutdown? (Check all that apply) IR Sump/Trench Sensors; 0 Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks and sensor failureldisconnection? 0 Yes; ❑No. <br /> 0 Yes 0 No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no <br /> ❑ N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank <br /> fill point(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? 901/6 <br /> ❑ Yes* 0 No Was any monitoring equipment replaced? If yes,identify specific sensors,probes,or other equipment replaced <br /> and list the manufacturer name and model for all replacement parts in Section E,below. <br /> ❑ Yes* 0 No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br /> ❑Product; ❑Water. If yes,describe causes in Section E,below. <br /> ❑ No* was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable <br /> YesQ No* I Is all monitoriLng 9guj2Ment 2ggEgonal pg manufacturees sMifications? <br /> In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: <br /> Page 2 of 4 <br />