Laserfiche WebLink
Form 1 <br /> Source Test Tesults <br /> Static Leak Test <br /> Date: 05/10/2000 Time: 14:00 Application No. <br /> GDF Name and address: 32262 2360 GRANTLINE,I-205 OFF RAMP <br /> Stage II system (check one): Vapor Balance [ ] Single Hose M.P.D. [X ] <br /> Vacuum Assist [X ] Type: GILBARCO <br /> Stage I type (check one): Two point [X ] Manifolded? Yes [ ] <br /> Coaxial [ ] No [ ] <br /> Tank# 1 2 3 <br /> Product grade REG PLS PRM <br /> Actual tank capacity (gallons) 15046 10028 10028 35102 <br /> Gasoline volume (gallons) 5639 7482 5696 18817 <br /> Ullage (gallons) 9407 2546 4332 16285 <br /> Initial pressure of UST, inches H2O 2 2 <br /> Number of nozzles served by tank 12 12 <br /> Test location: (A) Stage I vapor <br /> coupler of(B)Stage II riser A <br /> Initial Pressure, inches H2O (2.0) 2 <br /> Pressure after 1 min. (inches H2O) 1.99 <br /> Pressure after 2 min. (inches H2O) 1.98 <br /> Pressure after 3 min. (inches H2O) 1.97 <br /> Pressure after 4 min. (inches H2O) 1.96 <br /> Final Pressure after 5 min. (inches <br /> H2O) 1.95 <br /> Allowable Final Pressure: Table 1 A, <br /> Table 113,Equations 9.1, 9.2 1.93 <br /> Test Status [Pass or Fail] Pass <br /> Tests Conducted By: MLEVESQUE <br /> Test Company: TANKNOLOGY Date of Tests: 05/10/2000 <br /> Tests Witnessed By: N/A <br />