Laserfiche WebLink
Test Date: 12/30/2002 <br /> - Work Order. 2224985 <br /> SECONDARY CONTAINMENT TEST RESULTS <br /> SUMP TESTS <br /> Type Tank or Disp Manufacturer Model or Diam./Width/Length Depth Test Method Start Initial Level Finish Final Pass/ <br /> # Material (°) 1 (") I I Time Level Change Time Result Fail <br /> Dispenser Pan 1/2 Total Containment Plastic 25" 34" Hydrostatic-VPLT 1400 16" 0.06700 1416 1.605 Fail <br /> Dispenser Pan 3/4 Total Containment Plastic 25" 34" Hydrostatic-VPLT 1400 16" 0.06840 1416 1.630 Fail <br /> Dispenser Pan 5/6 Total Containment Plastic 25" 34" Hydrostatic-VPLT 1420 16" 0.07215 1436 1.392 Fail <br /> Dispenser Pan 7/8 Total Containment Plastic 25" 34" Hydrostatic-VPLT 1450 16 0.08229 1506 1.959 Fail <br /> Dispenser Pan 9/10 Total Containment Plastic 25" 34" Hydrostatic-VPLT 1530 16 0.08416 1546 2.003 Fail <br /> Dispenser Pan 11/12 Total Containment Plastic 25" 34" Hydrostatic-VPLT 1559 16 0.08629 1615 2.058 Fail <br /> Comments: <br />