Laserfiche WebLink
UL/ULC Listed RED T EAD° IIA Piping <br /> GENERAL SPECIFICATIONS <br /> Primary Piping Secondary Containment Piping <br /> SCOPE SCOPE <br /> PiPE-Pipe shall be manufactured by Smith Fibercast by PIPE- Pipe shall be manufactured by Smith Fibercast by <br /> a filament winding process using a thermosetting epoxy a filament winding process using a thermosetting epoxy <br /> resin to impregnate strands of continuous glass filaments resin to impregnate strands of continuous glass filaments <br /> which are wound around a mandrel at a prescribed helix which are wound around a mandrel at a prescribed helix <br /> angle and under controlled tension. .all pipe will be I angle and under controlled tension. <br /> supplied with matching tapered T.A.B." (Threaded and <br /> Bonded) coupling and spigot ends or T.A.B. spigot x CONSTRUCTION <br /> spigot ends. 3"-4"PIPE - RED THREAD IIA pipe shall have continuous <br /> CONSTRUCTION glass fibers filament wound at a 35 helix angle in a <br /> matrix of epoxy resin. Pipe shall be in compliance with <br /> 2"-4"PIPE- RED THREAD IIA pipe shall have continuous ASTN4 D2310 and classified by its designation code. Pipe <br /> glass fibers filament wound at a 351/',' helix angle in a shall meet all performance requirements and mechanical <br /> matrix of epoxy resin. Pipe shall be in compliance with properties, and shall be classified with the following <br /> ASTM D2310 and classified by its designation code. Pipe designation codes: <br /> shall meet all dimensional and performance Size Designation Code at 73.4'F <br /> requirements. mechanical properties, and shall be ; RTRP-11AE <br /> classified with the following designation codes: 4•• RTRP-11AF <br /> Size Designation Code at 73.4° F <br /> 2"-3" RTRP-11 AE ITEMS <br /> q RTRP•11AF 3"-4"PIPE - Glass fiber reinforced filament wound pipe <br /> with Plain end by Plain end. Pipe to be factory <br /> ITEMS prooftested at the following pressures: <br /> 2"-4"PIPE -Glass fiber reinforced filament wound pipe 3" -300 psig(minimum) <br /> with matching tapered T.A.B. (Threaded and Bonded) 4". 265 psis(minimum) <br /> coupling and spigot ends. Pipe to be factory prooftested <br /> at the following pressures: I 3"-4"FITTINGS -Compression molded two-piece fittings <br /> 2 -375 psis shall be manufactured using a vinyl ester molding <br /> u <br /> compound. The molding compond shall be reinforced <br /> 3"-300 psig j with a minimum of 60%chopped glass fiber. <br /> #--265 psig <br /> ADHESIVES -Adhesive and curing agents shall be either <br /> 2"-4"FITTINGS-Compression molded fittings shall be <br /> manufactured using an epoxy molding compound. The UL Listed DS-8000 or DS-7000 series adhesive. Consult <br /> molding compound shall be reinforced with a minimum Smith Fibercast's installation manual No. 62160 for <br /> of 459%chopped glass fiber. In-line fittings are filament recommended heat curing techniques. <br /> wound. I JOINING TECHNIQUES <br /> ADHESIVES- Adhesive and curing agents shall be either I 3"-4"PIPE and FITTINGS- Pipe shall be joined with <br /> UL Listed DS-8000 or DS-7000 series adhesive. either DS-8000 or DS-7000 series adhesive. Fittings shall <br /> Consult Smith Fibercast's installation manual No. B2160 be joined with either DS-7000 or DS-8000 series <br /> for recommended heat curing techniques. adhesives and filler. Material to be installed in <br /> accordance with Smith Fibercast's installation manual <br /> JOINING TECHNIQUES No. B2160. <br /> 2"-4"PIPE and FITTINGS-Pipe and fittings shall be TESTING <br /> joined with DS-8000 or DS-7000 series adhesive using <br /> matching tapered bell/coupling and spigot. Material to 3"-4"SECONDARY CONTAINMENT PIPE SYSTEMS- <br /> be installed in accordance with Smith Fibercast's Secondary containment pipe systems should be tested <br /> installation manual No. 82160. prior to use to assure soundness of all joints and <br /> connections. Consult Smith Fibercast's installation <br /> TESTING manual No. 82160. <br /> 2"-4"PRIMARY PIPE SYSTEMS-Primary pipe systems <br /> should be tested prior to use to assure soundness of all <br /> joints and connections. Consult Smith Fibercast's <br /> installation manual No. B2160. <br />