Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for 7-ELEVEN INC #32262 as of April 17, 2018. <br /> Open violations from March 02, 2018 inspection <br /> Violation #105 -Failed to have an approved UST monitoring plan. <br /> The monitoring plan is not current and/or not approved by the EHD. The monitoring plan is not current for the 89 <br /> tank for the mechanical line leak detector. The monitoring plan must be uploaded to the California Environmental <br /> Reporting System (CERS). Immediately log into CERS, make the necessary changes, and submit for review by the <br /> EHD. <br /> Violation #107 -Plot plan/site map not submitted or failed to completely show where monitoring is <br /> performed. <br /> An accurate UST Monitoring Site Plan was not submitted. The legend for the site plan is inaccurate for the tank <br /> diagram and for the line leak detector on the 89 STP sump. A site plan must be submitted identifying the locations <br /> where monitoring will be performed. Immediately log into the California Environmental Reporting System (CERS) at <br /> http://cers.calepa.ca.gov/and upload a copy of the UST Monitoring Site Plan. <br /> Violation#315 -Water in secondary containment not removed, analyzed, and properly disposed of(pre-Jul <br /> 2003). <br /> Liquid was observed in the 89 and 91 fill sumps. If water could enter into the secondary containment by <br /> precipitation or infiltration, it must be removed and disposed of properly. The service technician removed about 10 <br /> cups of liquid from the 89 fill sump and about 8 cups of liquid from the 91 fill sump. Ensure that all sumps are <br /> maintained free of liquid. <br /> This was corrected on site. <br /> Page 1 of 1 <br />