Laserfiche WebLink
6. PIPING SUMP TESTING <br /> Test Method Developed By: ❑Sump Manufacturer ❑✓ Industry Standard ❑Professional Engineer <br /> [-]Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum ❑✓ Hydrostatic <br /> E]Other(Spec) <br /> Test Equipment Used: See attached testing procedures Equipment Resolution: Inches <br /> ENNOME Sump# 87 Sump# 91 Sump# Sump# <br /> Sump Diameter: 48" 48" <br /> Sump Depth: 78" 78" <br /> Sump Material: Fiberglass Fiberglass <br /> Height from Tank Top to flop of 12" 12" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 25" 27" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Fair Fair Fair Fair <br /> Portion of Sump Tested' Above highest penetration Above highest penetration Above highest penetration Above highest penetration <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ❑Yes []No ❑✓NA ❑Yes []No ❑✓NA ❑Yes[] No M NA ❑Yes ❑(vo ✓❑NA <br /> product and water)?* <br /> Turbine shutdown response time N/A N/A I N/A N/A <br /> Is system programmed for fail-safe ❑ ❑ []Yes ❑No ❑ ElYes❑ No[Z]NA [:1 Yes []NoR✓NA <br /> shutdown?` ❑Yes No NA NA <br /> Was fail-safe verified to be <br /> o erational?' []Yes ❑No ❑✓NA [:]Yes ❑No ✓❑NA [-]Yes ❑No ❑✓NA [1 Yes [:]No �✓NA <br /> Wait time between applying <br /> pressure/vacuum/water and starting 15 minutes 15 minutes 15 minutes 15 minutes <br /> test: <br /> Test Start Time: 10:54am 10:53am <br /> Initial Reading(RI): 4.18182 Inches 0.98256 Inches Inches Inches <br /> Test End Time: 11:09am 11:08am <br /> Final Reading(RF): 4.18163 Inches 0.98259 Inches Inches Inches <br /> Test Duration: 15 mins 15 mins 15 mins 15 mins <br /> Change in Reading(RF-R,): 0.00019 0.00003 <br /> Pass/Fail Threshold or Criteria: 0.002 0.002 0.002 0.002 <br /> Test Result: ❑✓ Pass ❑Fail ❑✓ Pass ❑Fail ❑Pass ❑Fail ❑Pass ❑Fail <br /> Was sensor removed for testing? Oyes ❑No [INA Eyes ❑No [INA ❑✓ Yes ❑No ❑NA ❑✓ Yes ❑No ❑NA <br /> Was sensor properly replaced and ❑✓Yes ❑No []NA ❑✓ Yes E]No ❑NA ✓❑Yes []No ❑NA ❑✓ Yes []No []NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing,and recommended follow-up for failed tests) <br />