Laserfiche WebLink
v2w2 vvaiton tngineenng, Inc. <br />Sa�`J✓'�c � O <br />WALTON PRODUCT LINE TESTING�. � �' . <br />ENGINEERING,, INC. DATA SHEET sys�m8arrelning <br />for the <br />` Petroleum Industry <br />Facility: Market Place Test Equipment Used: EZY Product Line Tester <br />Address: 4405 Pacific Avenue, Stockton, CA 95207 Test Method By: Manufacturer <br />Test Date: 110 Test Pressure Used: 50 psi [1% x Operating Pressure] <br />Line #: 1 Product: Gasoline - 87 (UDC's 9 -12) Diameter. 2 <br />Manufacturer. AO SmithMaterial: FRP Leak Detector Yes <br />Monitor Mode: <br />Time Time Elapsed Test Level Test Level Change Conversion Gain/(Loss) Rate <br />Start End Time Start End in Level Factor [Gallons] <br />Test Mode: <br />Time Time Elapsed Test Level Test Level Change Conversion Gain/(Loss) Rate <br />Start End Time Start End in Level Factor [Gallons] [G.P.H.] <br />9:52 AM 10:07 AM 62 <br />9:52 AM 10:07 AM 0:15 62 61.5 -0.5 0.0037 -0.0019 N/A <br />10:07 AM 10:22 AM 0:15 61.5 61 -0.5 0.0037 -0.0019 N/A <br />9:52 AM 10:22 AM 0:30 62 61 -1 0.0037 -0.0037 -0.0037 <br />Pass / Fail Threshold =.05 G.P.H TEST RESULT = PASS <br />Comments: <br />This is a primary product line test on the 87 primary line to dispensers 9 thru 12. <br />v2w2 vvaiton tngineenng, Inc. <br />