Vaporless Mfg. LD 3000/3000S <br /> 4.0 Test Results and Discussion <br /> Table 3. Evaluation of the Vaporless LD 3000, Tested on Large Rigid Pipelines- <br /> 3.0 gal/hr Leak Tests, Pipe Line Leak Detection System, Options 1 & 5 <br /> Data Summarizing the Product Temperature Conditions Used in the Evaluation <br /> Test No. Date Nominal Time Time Duration of Time of T(TB) T(1) T(2) T(3) T(G) T(TB)-T(G) Temperature <br /> Test Product Circulation Circulation Circulation Temperature Test <br /> Began Temperature Started Ended Measurements Matrix <br /> Before Category <br /> Circulation <br /> Was Started <br /> (D-M-Y) (deg F) (local military) (local military) (h-min) (local military) (deg F) (deg F) (deg F) (deg F) (deg F) (deg F) (Table 5.1) <br /> 1 23-Sep-05 94.6 14:35 15:35 1:00 14:35 94.6 67.9 68.2 68.3 68.3 26.3 -25 <br /> 2 23-Sep-05 94.6 14:35 15:35 1:00 14:35 94.6 67.9 68.2 68.3 68.3 26.3 -25 <br /> 3 26-Sep-05 42 12:08 13:08 1:00 12:08 42 68.4 68.3 68.3 68.3 -26.3 <-25 <br /> 4 26-Sep-05 42 12:08 13:08 1:00 12:08 42 68.4 68.3 68.3 68.3 -26.3 <-25 <br /> 5 26-Sep-05 67.5 14:00 15:00 1:00 14:00 67.5 64.2 67.4 68.1 67.5 0 -5 to+5 <br /> 6 26-Sep-05 67.5 14:00 15:00 1:00 14:00 67.5 64.2 1 67.4 68.1 67.5 0 -5 to+5 <br /> Data Summarizing the Test Results and the Leak Rates Used in the Evaluation <br /> Test No. Date Induced Time between End Time Data Time Data Measured Was <br /> (Based on Test Leak Rate of Circulation and Collection Collection Test Threshold <br /> Temperature Began Start of Data Began Ended Result Exceeded? <br /> Condition) Collection for Test <br /> D-M-Y al/h) (h-min local milita local milita leak or ti ht es or no <br /> 1 23-Sep-05 0.0 9 15:44 15:44 0.0 no <br /> 2 23-Sep-05 3.0 10 15:45 15:46 3.0 yes <br /> 3 26-Sep-05 0.0 0 13:08 13:08 0.0 no <br /> 4 26-Sep-05 3.0 1 13:09 13:10 3.0 yes <br /> 5 26-Sep-05 0.0 4 15:04 15:04 0.0 no <br /> 6 26-Sep-05 3.0 4 15:04 15:05 3.0 yes <br /> Page 4 of 8 <br />