Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 7. UNDER-DISPENSER CONTAINMENT DC TESTING <br /> Test Method Developed By: UDC Manufacturer x Industry Standard Professional Engineer <br /> Other(Specify) <br /> Test Method Used: Pressure Vacuum x Hydrostatic <br /> Other(Specify) <br /> Test Equipment Used:Incon TS-STS Equipment Resolution: <br /> UDC#16/17 UDC#14/15 UDC#13 UDC#21 Sat. <br /> UDC Manufacturer: Western Fiberglass Western Fiberglass Western Fiberglass Western Fiberglass <br /> UDC Material: FRP FRP FRP FRP <br /> UDC Depth: 31" 31" 31" 31" <br /> Height from UDC Bottom to Top 6" 6" 6" 8" <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 9" 4" 3" 6" <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to OK OK OK OK <br /> testing: <br /> Portion of UDC Tested 2"above highest pipe 2"above highest 2"above highest pipe 2"above highest pipe <br /> en. pipe pen. pen. pen. <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both Yes No x NA Yes No x NA Yes No x NA Yes No x NA <br /> _product and water)?" <br /> Turbine shutdown response time <br /> Is system programmed for fail- Yes No x NA Yes No x NA Yes No x NA Yes No x NA <br /> safe shutdown?* <br /> Was fail-safe verified to be Yes No x NA Yes No x NA Yes No x NA Yes No x NA <br /> -operational?* <br /> Wait time between applying 15 Minutes 15 Minutes 15 Minutes 15 Minutes <br /> pressure/vacuum/water and <br /> -starting test <br /> Test Start Time: 4:24 pm—4:40 pm 4:24 pm—4:40 pm 4:24 am—4:40 am 9:34 am—9:52 am <br /> Initial Reading (RI): 3.6082—3.6076 3.9912—3.9906 4.1313—4.1307 3.5265—3.5269 <br /> Test End Time: 1 4:39 pm—4:55 pm 4:39 m—4:55 pm 4:39 am—4:55 am 9:49 am—10:07 am <br /> Final Reading (RF): 3.6076—3.6077 3.9905—3.9907 4.1307—4.1307 3.5269—3.5272 <br /> Test Duration: 15 Min Each(30)Min 15 Min Each(30) 15 Min Each(30)Min 15 Min Each(30)Min <br /> Min <br /> Chane in Reading RF-RI : .0006-.0001 .0007-.0001 .0006-0 .0004-.0003 <br /> Pass/Fail Threshold or Criteria: .002 .002 .002 .002 <br /> est Result: x Pass 0 Fail x Pass 0 Fail x Pass ❑Fail x Pass ❑Fail <br /> Was sensor removed for testing? x Yes No NA x Yes No NA x Yes No NA x Yes No NA <br /> Was sensor properly replaced and x Yes No NA x Yes No NA x Yes No NA x Yes No NA <br /> verified functional after testin ? <br /> Comments—(include information on repairs made prior to testing,and recommended follow-up for failed tests) <br /> In dispenser #16/17 we installed a new secondary test boot on the 87 Droduct. <br /> In dispenser #14/15 we sealed up the gaps on the bottom and side of the udc. <br /> In dispenser #13 we installed a new secondary test boot on the 91 product. <br /> 'If the entire depth of the UDC is not tested,specify how much was tested. If the answer to_yof the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />