ELECTRICAL ELECTRICAL ELECTRICAL ELECTRICAL
<br /> SECTION 260519 - LOW-VOLTAGE (600V OR LESS) ELECTRICAL POWER CONDUCTORS AND CABLES SECTION 260533 -RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS SECTION 260553 -IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 262726-WIRING DEVICES
<br /> 1.1 MATERIALS PART 1 - GENERAL 1.1 QUALITY ASSURANCE 1.1 PRODUCTS n
<br /> A. CONDUCTORS AND CABLES: A. COMPLY WITH ANSI A13.1 AND IEEE C2. A. RECEPTACLES: DUPLEX, 125 V, 20 A.
<br /> 1. CONDUCTORS: COPPER. 1.1 MATERIALS 1. STRAIGHT BLADE: CONVENIENCE AND ISOLATED GROUND.
<br /> 2. CONDUCTOR INSULATION: TYPE THHN/THWN-2, TYPE XHHW-2, TYPE USE AND A. METAL CONDUITS, TUBING, AND FITTINGS: 1.2 PRODUCTS 2. GFCI: FEED THROUGH.
<br /> TYPE SO. 1. GRC. A. POWER AND CONTROL RACEWAY IDENTIFICATION:VINYL LABELS 3. TWIST-LOCKING TYPE WITH ISOLATED-GROUND TERMINAL.
<br /> 3. MULTICONDUCTOR CABLE: METAL-CLAD CABLE, TYPE MC WITH GROUND WIRE. 2. EMT. B. PENDANT CORD-CONNECTOR DEVICES WITH EXTERNAL CABLE GRIP.
<br /> 3. FMC: ZINC-COATED STEEL. B. POWER AND CONTROL CABLE IDENTIFICATION:VINYL LABELS C. CORD AND PLUG SETS: MATCH VOLTAGE AND CURRENT RATINGS AND NUMBER OF
<br /> 1.2 CONDUCTOR MATERIAL APPLICATIONS 4. LFMC. CONDUCTORS TO REQUIREMENTS OF EQUIPMENT BEING CONNECTED. 0
<br /> A. FEEDERS: COPPER. SOLID FOR NO. 10 AWG AND SMALLER; STRANDED FOR NO. 8 AWG 5. FITTINGS: C. CONDUCTOR IDENTIFICATION: D. TOGGLE SWITCHES: 120/277 V, 20 A.
<br /> AND LARGER. a. EMT: STEEL, SETSCREW OR COMPRESSION TYPE. SNAP-AROUND LABELS. 1. PILOT-LIGHT SWITCHES. ©2020 STARBUCKS COFFEE COMPANY
<br /> B. BRANCH CIRCUITS: COPPER. SOLID FOR NO. 12 AWG AND SMALLER; STRANDED FOR b. EXPANSION FITTINGS. 2. KEY-OPERATED SWITCHES.
<br /> NO. 10 AWG AND LARGER, EXCEPT VFC CABLE, WHICH SHALL BE EXTRA FLEXIBLE B. NONMETALLIC CONDUITS, TUBING, AND FITTINGS: D. FLOOR MARKING TAPE: 2-INCH- (50-MM-)WIDE PRESSURE-SENSITIVE VINYL TAPE. E. WALL-BOX DIMMERS:
<br /> STRANDED. 1. RNC. E. UNDERGROUND-LINE WARNING TAPE:PIGMENTED POLYOLEFIN 1. MODULAR, FULL-WAVE, SOLID-STATE UNITS WITH SLIDER CONTROL. STA R B V C KS°
<br /> 2. FITTINGS: MATCH CONDUIT. a. INCANDESCENT: SOFT TAP OR OTHER QUIET SWITCH; EMI/RFI
<br /> 1.3 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND WIRING 3. SOLVENT CEMENTS AND ADHESIVE PRIMERS SHALL HAVE A VOC CONTENT OF F. WARNING LABELS AND SIGNS:SELF-ADHESIVE WARNING LABELS. FILTER TO ELIMINATE INTERFERENCE. 2401 UTAH AVENUE SOUTH
<br /> METHODS 510 AND 550 G/L OR LESS, RESPECTIVELY. b. FLUORESCENT: TRIM POTENTIOMETER FOR LOW-END DIMMING. SEATTLE, WASHINGTON 98134
<br /> A. SERVICE ENTRANCE: TYPE THHN/THWN-2, SINGLE CONDUCTORS IN RACEWAY. C. METAL WIREWAYS AND AUXILIARY GUTTERS: SHEET METAL WITH G. INSTRUCTION SIGNS:ENGRAVED. c. LED: COMPATIBLE WITH LED DRIVER OR LAMP.
<br /> B. EXPOSED FEEDERS: TYPE THHN/THWN-2, SINGLE CONDUCTORS IN RACEWAY. SCREW COVERS. F. WALL PLATES: (2O6) 318-1575
<br /> C. FEEDERS CONCEALED IN CEILINGS, WALLS, PARTITIONS,AND CRAWLSPACES: D. SURFACE METAL RACEWAYS: METAL, GALVANIZED STEEL, WITH SNAP-ON COVERS. H. EQUIPMENT IDENTIFICATION LABELS:ENGRAVED, LAMINATED 1. MATERIAL FOR WORKROOM:
<br /> METAL-CLAD CABLE. E. BOXES, ENCLOSURES, AND CABINETS: ACRYLIC OR MELAMINE PLASTIC. SATIN-FINISHED STAINLESS STEEL. THESE DRAWINGS AND THE PROJECT MANUAL
<br /> D. FEEDERS CONCEALED IN CONCRETE, BELOW SLABS-ON-GRADE, AND UNDERGROUND: 1. METAL OUTLET AND DEVICE BOXES:FERROUS ALLOY 2. MATERIAL FOR BAR: ARE CONFIDENTIAL AND SHALL REMAIN THE
<br /> TYPE THHN/THWN-2, SINGLE CONDUCTORS IN RACEWAY. 2. METAL FLOOR BOXES: CAST METAL OR SHEET METAL, FULLY END OF SECTION 260553 SATIN-FINISHED STAINLESS STEEL. SOLE PROPERTY OF STARBUCKS
<br /> E. EXPOSED BRANCH CIRCUITS, INCLUDING IN CRAWLSPACES: TYPE THHN/THWN-2, ADJUSTABLE. 3. MATERIAL FOR CUSTOMER AREAS:THERMOPLASTIC WITH COLOR OPTION PER CORPORATION, WHICH IS THE OWNER OF THE
<br /> SINGLE CONDUCTORS IN RACEWAY. 3. LUMINAIRE OUTLET BOXES: NONADJUSTABLE, DESIGNED FOR ATTACHMENT OF STARBUCKS. COPYRIGHT IN THIS WORK. THEY SHALL NOT
<br /> F. BRANCH CIRCUITS CONCEALED IN CEILINGS, WALLS, AND PARTITIONS: TYPE LUMINAIRE WEIGHING 50 LB (23 KG). G. FLOOR SERVICE FITTINGS: MODULAR, (DUAL SERVICE IF NEEDED), WITH POWER BE REPRODUCED (IN WHOLE OR IN PART),
<br /> THHN/THWN-2, SINGLE CONDUCTORS IN RACEWAY. 4. SMALL SHEET METAL PULL AND JUNCTION BOXES. ELECTRICAL RECEPTACLE (AND VOICE AND DATA COMMUNICATION OUTLET IF NEEDED). SHARED WITH THIRD PARTIES OR USED IN ANY
<br /> G. BRANCH CIRCUITS CONCEALED IN CONCRETE, BELOW SLABS-ON-GRADE, AND 5. CAST-METAL ACCESS, PULL,AND JUNCTION BOXES. 1. TYPE:FLUSH MANNER ON OTHER PROJECTS OR
<br /> UNDERGROUND: TYPE THHN/THWN-2, SINGLE CONDUCTORS IN RACEWAY. 6. BOX EXTENSIONS. SECTION 260923 -LIGHTING CONTROL DEVICES 2. SERVICE PLATE:RECTANGULAR. EXTENSIONS TO THIS PROJECT WITHOUT THE
<br /> H. CORD DROPS AND PORTABLE APPLIANCE CONNECTIONS: TYPE SO, HARD 7. GANGABLE BOXES ARE PROHIBITED. 3. VOICE AND DATA COMMUNICATION OUTLET: BLANK COVER WITH BUSHED CABLE PRIOR WRITTEN CONSENT OF STARBUCKS
<br /> SERVICE CORD WITH STAINLESS-STEEL, WIRE-MESH, STRAIN RELIEF DEVICE AT 8. HINGED-COVER ENCLOSURES: METAL. 1.1 PRODUCTS OPENING. CORPORATION. THESE DRAWINGS AND
<br /> TERMINATIONS TO SUIT APPLICATION. 9. CABINETS: GALVANIZED STEEL. A. TIME SWITCHES:ELECTRONIC, PROGRAMMABLE UNITS, WITH SINGLE CHANNEL; H. POKE-THROUGH ASSEMBLIES: BELOW-FLOOR JUNCTION BOX WITH MULTICHANNELED, SPECIFICATIONS ARE INTENDED TO EXPRESS
<br /> F. HANDHOLES AND BOXES FOR EXTERIOR UNDERGROUND WIRING: POLYMER ASTRONOMIC TIME, SEVEN-DAY THROUGH-FLOOR RACEWAY/FIRESTOP AND DETACHABLE FLOOR SERVICE-OUTLET DESIGN INTENT FOR A PROTOTYPICAL
<br /> 1.4 FIELD QUALITY CONTROL CONCRETE WITH POLYMER-CONCRETE FRAME AND COVER, PROTOTYPE TESTED PROGRAMMABLE WITH MINIMUM 8 ON/OFF SET POINTS PER 24 HOUR ASSEMBLY. STARBUCKS STORE (WHICH IS SUBJECT TO
<br /> A. TESTING: BY CONTRACTOR. FOR COMPLIANCE WITH SCTE 77. SCHEDULE. 1. SERVICE-OUTLET ASSEMBLY: SURFACE TYPE. CHANGE AT ANYTIME)AND DO NOT REFLECT
<br /> 1. CONFIGURATION: INTEGRAL CLOSED BOTTOM. B. OUTDOOR PHOTOELECTRIC SWITCHES: SOLID STATE, WITH DRY CONTACTS, 2. SIZE:4 INCHES (100 MM). ACTUAL SITE CONDITIONS. NEITHER PARTY
<br /> END OF SECTION 260519 2. WEATHERPROOF COVER. 15-SECOND TIME DELAY, AND METAL-OXIDE VARISTOR SURGE PROTECTION. I. MULTIOUTLET ASSEMBLIES: MANUFACTURED AND LISTED METAL RACEWAYS. SHALL HAVE ANY OBLIGATION NOR LIABILITY TO
<br /> 3. COVER LEGEND:"ELECTRIC." C. DAYLIGHT-HARVESTING SWITCHING CONTROLS: CEILING MOUNTED WITH J. SERVICE POLES: TO EXTEND POWER AND VOICE AND DATA COMMUNICATION
<br /> ADJUSTABLE TIME DELAY AND SET-POINTS. WIRING FROM DISTRIBUTION WIRING IN CEILING TO DEVICES OR OUTLETS IN POLE THE OTHER (EXCEPT STATED ABOVE) UNTIL A
<br /> 1.2 RACEWAY APPLICATION D. INDOOR OCCUPANCY SENSORS:DUAL-TECHNOLOGY TYPE, NEAR FLOOR. WRITTEN AGREEMENT IS FULLY EXECUTED BY
<br /> A. OUTDOORS: WITH SEPARATE, EXTERNALLY MOUNTED RELAY UNIT. 1. FINISH: PAINTED. BOTH PARTIES.
<br /> ELECTRICAL 1. EXPOSED: GRC. E. SWITCH BOX-MOUNTED OCCUPANCY SENSORS. 2. POWER RECEPTACLES: TWO, DUPLEX, 20 A.
<br /> 2. CONCEALED,ABOVEGROUND: RNC, TYPE EPC-40-PVC. F. LIGHTING CONTACTORS: ELECTRICALLY OPERATED AND 3. VOICE AND DATA COMMUNICATION OUTLETS:BLANK INSERT STARBUCKS TEMPLATE VERSION: i2020.10.23
<br /> SECTION 260526 -GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 3. UNDERGROUND: RNC, TYPE EPC-40-PVC, DIRECT BURIED. ELECTRICALLY HELD, WITH NONFUSED DISCONNECT IN
<br /> 4. CONNECTION TO VIBRATING EQUIPMENT: LFMC. NEMA 250 ENCLOSURE. PROVIDE WITH CONTROL AND PILOT DEVICES AS K. FINISHES:
<br /> 1.1 QUALITY ASSURANCE 5. BOXES AND ENCLOSURES, ABOVEGROUND: TYPE 3R OR TYPE 4. INDICATED IN PLANS. 1. CONNECTED TO NORMAL POWER SYSTEM:WHITE
<br /> A. QUALITY STANDARD FOR GROUNDING AND BONDING MATERIALS AND B. INDOORS: G. EMERGENCY SHUNT RELAY: NORMALLY CLOSED, ELECTRICALLY HELD, architecture
<br /> EQUIPMENT: UL 467. 1. EXPOSED, NOT SUBJECT TO PHYSICAL DAMAGE: GRC. ARRANGED FOR WIRING IN PARALLEL WITH AUTOMATIC 2. CONNECTED TO EMERGENCY POWER SYSTEM: RED . interiors
<br /> 2. EXPOSED, NOT SUBJECT TO SEVERE PHYSICAL DAMAGE: EMT. SWITCHING CONTACTS. 3. ISOLATED-GROUND RECEPTACLES: AS SPECIFIED ABOVE, WITH and
<br /> 1.2 PRODUCTS 3. CONCEALED: EMT. H. CONTROL CABLES: ORANGE TRIANGLE ON FACE.
<br /> A. INSULATED CONDUCTORS: COPPER WIRE OR CABLE. 4. CONNECTION TO VIBRATING EQUIPMENT: FMC, EXCEPT LFMC IN DAMP OR WET 1. POWER CABLES: NOT SMALLER THAN NO. 12 AWG.
<br /> B. BARE COPPER CONDUCTORS: LOCATIONS. 2. CLASSES 2 AND 3 CONTROL CABLES: STRANDED-COPPER CONDUCTORS, NOT END OF SECTION 262726 5858 Wilshire Blvd #200 T: 323.954.8996
<br /> 1. SOLID CONDUCTORS. 5. DAMP OR WET LOCATIONS: GRC. SMALLER THAN NO. 18 AWG.
<br /> 2. STRANDED CONDUCTORS. 6. BOXES AND ENCLOSURES: TYPE 1, EXCEPT TYPE 4 STAINLESS STEEL 3. CLASS 1 CONTROL CABLES: STRANDED-COPPER CONDUCTORS, NOT SMALLER Los Angeles, CA 90036 F: 323.954.8965
<br /> 3. TINNED CONDUCTORS. IN DAMP OR WET LOCATIONS. THAN NO. 14 AWG. ELECTRICAL
<br /> 4. STRANDED BONDING CONDUCTORS. C. MINIMUM RACEWAY SIZE: 3/4-INCH TRADE SIZE. WWW.valerioinc.com * info@valerioinc.com
<br /> 5. COPPER TAPE BRAIDED BONDING JUMPERS. D. RACEWAY FITTINGS: COMPATIBLE WITH RACEWAYS AND SUITABLE FOR USE AND END OF SECTION 260923
<br /> 6. TINNED-COPPER BRAIDED BONDING JUMPERS. LOCATION. SECTION 262816 -ENCLOSED SWITCHES AND CIRCUIT BREAKERS
<br /> C. CONNECTORS: BOLTED AND EXOTHERMIC-WELDED TYPE. 1. RIGID AND INTERMEDIATE STEEL CONDUIT: THREADED RIGID STEEL CONDUIT 1.1 PRODUCTS tit
<br /> D. GROUNDING ELECTRODES: FITTINGS. FESS/ tiiZ
<br /> 1. GROUND RODS: COPPER-CLAD STEEL, SECTIONAL TYPE WITH GROUND WELL 2. PVC EXTERNALLY COATED, RIGID STEEL CONDUITS: FITTINGS LISTED FOR A. FUSIBLE SWITCHES: r�~�PROAV 20,yq� ,
<br /> ELECTRICAL 1. GENERAL DUTY, SINGLE THROW, [240-V] [600V]AC, 800 A AND SMALLER: UL 98 ACIES rr�� ,S� t2
<br /> AND COVER. USE WITH THIS TYPE OF CONDUIT.
<br /> AND NEMA KS 1, NEMA 3R TYPE GD. r 0 s ?
<br /> 3. EMT: COMPRESSION FITTINGS. SECTION 262416- PANELBOARDS 2. ACCESSORIES: ENGINEERING
<br /> 1.3 FIELD QUALITY CONTROL 4. FLEXIBLE CONDUIT: FITTINGS LISTED FOR USE WITH FLEXIBLE CONDUIT. 30 �1
<br /> a. EQUIPMENT GROUND KIT. 400NMcCarthyBlvd. t 1
<br /> A. GROUND RESISTANCE TESTING: BY CONTRACTOR-ENGAGED AGENCY. 1.1 QUALITY ASSURANCE Suite 250,Milpitas,CA 95035
<br /> b. NEUTRAL KIT. ,�
<br /> END OF SECTION 260533 A. MANUFACTURER QUALIFICATIONS: ISO 9001 OR 9002 CERTIFIED. c. ISOLATED GROUND KIT. ph:(408)522-5255 ttt r�gl�FCTR�GP���rrr
<br /> END OF SECTION 260526 fx:(408)522-5260
<br /> 111E pp p��EO���
<br /> d. CLASS R FUSE KIT. Ztiti c ~
<br /> 1.2 PRODUCTS info@acies.net
<br /> A. GENERAL REQUIREMENTS FOR PANELBOARDS: e. AUXILIARY CONTACT KIT. Copyright©2021
<br /> 1. CONSTRUCTED TO WITHSTAND SEISMIC FORCES. f. HOOKSTICK HANDLE.
<br /> ELECTRICAL 2. ENCLOSURES: SURFACE MOUNTED. q. LUGS- MECHANICAL.
<br /> h. SERVICER TED SWITCHES.
<br /> ELECTRICAL
<br /> a. FRONT: HINGED COVER WITH KEY LOCK. i. ACCESSORY CONTROL POWER.
<br /> SECTION 260536 -CABLE TRAYS FOR ELECTRICAL SYSTEMS b. OPTIONAL ENCLOSURE FEATURES:SKIRT FOR SURFACE-MOUNTED B. NONFUSIBLE SWITCHES:
<br /> DIRECTORY
<br /> 1.1 CABLE TRAY TYPES c. DIRECTTORY CAARD.
<br /> SECTION 260529 -HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PANELBOARDS. 1. GENERAL DUTY, SINGLE THROW, [240-V] [600V]AC, 600 A AND SMALLER: UL 98 1.1 PERFORMANCE REQUIREMENTS A. LADDER. 3. INCOMING MAINS:CONVERTIBLE BETWEEN TOP AND BOTTOM AND NEMA KS 1, NEMA 3R TYPE GD.
<br /> ACCESSORIES:
<br /> A. DESIGN SUPPORTS FOR MULTIPLE RACEWAYS CAPABLE OF SUPPORTING B. SINGLE RAIL. 4. PHASE, NEUTRAL AND GROUND BUSES: TIN-PLATED COPPER. 2. ACCESSORIES:
<br /> GROUND KIT.
<br /> COMBINED WEIGHT OF SUPPORTED SYSTEMS AND ITS CONTENTS. C. TROUGH. 5. CONDUCTOR CONNECTORS: a.b. NEUTRAL KIT.
<br /> B. DESIGN EQUIPMENT SUPPORTS CAPABLE OF SUPPORTING COMBINED OPERATING a. MATERIAL: TIN-PLATED COPPER. c. ISOLATED GROUND KIT.
<br /> WEIGHT OF SUPPORTED EQUIPMENT AND CONNECTED SYSTEMS AND 1.2 MATERIALS b. MAIN AND NEUTRAL LUGS: MECHANICAL TYPE. CONTACT KIT.
<br /> RY
<br /> COMPONENTS. A. CABLE TRAYS, FITTINGS, AND ACCESSORIES: STEEL. c. FEED-THROUGH LUGS: MECHANICAL TYPE. e. HC. AUXILIARY
<br /> HANDLE.
<br /> 1. FACTORY-STANDARD PRIMER; WITH CHROMIUM-ZINC-PLATED HARDWARE. 6. PERCENTAGE OF FUTURE SPACE CAPACITY:FIFTEEN LUGS: MECHANICAL.
<br /> 1.2 PRODUCTS 2. MILL GALVANIZED BEFORE FABRICATION; WITH PERCENT. f.f. ACCESSORY CONTROL POWER.
<br /> A. SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS: GALVANIZED HARDWARE. 7. SERVICE EQUIPMENT LABEL FOR PANELBOARDS INCORPORATING ONE OR MORE g.
<br /> 1. STEEL SLOTTED SUPPORT SYSTEMS WITH 3. ELECTROGALVANIZED BEFORE FABRICATION; WITH GALVANIZED HARDWARE. MAIN SERVICE DISCONNECTING AND OVERCURRENT PROTECTIVE DEVICES. C. MOLDED-CASE CIRCUIT BREAKERS:
<br /> METALLIC COATINGS. 4. HOT-DIP GALVANIZED AFTER FABRICATION; WITH B. PANELBOARD OR LOAD CENTER SHORT-CIRCUIT CURRENT RATING: FULLY RATED 1. THERMAL-MAGNETIC TYPE.
<br /> 2. NONMETALLIC SLOTTED SUPPORT SYSTEMS. CHROMIUM-ZINC-PLATED HARDWARE. TO INTERRUPT SYMMETRICAL SHORT-CIRCUIT CURRENT AVAILABLE AT TERMINALS. 2. ADJUSTABLE INSTANTANEOUS-TRIP TYPE.
<br /> 3. RACEWAY AND CABLE SUPPORTS. 5. POWDER-COAT ENAMEL PAINT; WITH CHROMIUM-ZINC-PLATED LISTED SERIES RATED SYSTEM MAY BE USED IF APPROVED BY EOR TO LIMIT FAULT 3. ELECTRONIC-TRIP TYPE. r z
<br /> 4. STEEL AND MALLEABLE-IRON CONDUIT AND CABLE HANGERS, CLAMPS, AND HARDWARE. TO BELOW 22K AIC FOR GFI BREAKERS. 4. CURRENT-LIMITING TYPE.
<br /> ASSOCIATED ACCESSORIES. 6. BLACK OXIDE FINISH FOR SUPPORT ACCESSORIES AND MISCELLANEOUS 1. MAINS: LUGS ONLY. 5. INTEGRALLY FUSED TYPE. � O
<br /> 5 .SUPPORT FOR NON-ARMORED CONDUCTORS AND CABLES IN VERTICAL HARDWARE. 2. BRANCH OVERCURRENT PROTECTIVE DEVICES FOR CIRCUIT-BREAKER FRAME 6. GFCI TYPE.
<br /> GFEP TYPE.
<br /> CONDUIT RISERS. 7. BLACK. SIZES LARGER THAN 125 A: BOLT-ON CIRCUIT BREAKERS. 7. W Q U
<br /> 6. STRUCTURAL STEEL FOR FABRICATED SUPPORTS AND RESTRAINTS. B. CABLE TRAYS, FITTINGS, AND ACCESSORIES: ALUMINUM; WITH STAINLESS-STEEL 8. FEATURES AND ACCESSORIES:
<br /> C. LIGHTING AND APPLIANCE BRANCH-CIRCUIT PANELBOARDS: a. LUGS: MECHANICAL. Uj >- U z
<br /> 7. MOUNTING, ANCHORING, AND ATTACHMENT COMPONENTS: HARDWARE. O _
<br /> 1. MAINS: LUGS ONLY. b. TYPE SWD FOR SWITCHING FLUORESCENT LIGHTING LOADS. � Cn
<br /> a. POWDER-ACTUATED FASTENERS. C. CABLE TRAY ACCESSORIES: 2. BRANCH OVERCURRENT PROTECTIVE DEVICES: PLUG-IN CIRCUIT-BREAKER c. TYPE HID FOR FEEDING FLUORESCENT AND HIGH-INTENSITY DISCHARGE LU - z
<br /> b. MECHANICAL-EXPANSION ANCHORS. 1. COVERS:LOUVERED TYPE. TYPE. LIGHTING CIRCUITS. LIJ � Z
<br /> c. CONCRETE INSERTS. 2. BARRIER STRIPS. 3. DOORS: CONCEALED HINGE. d. GROUND-FAULT PROTECTION: INTEGRALLY MOUNTED, SELF-POWERED TYPE. 2Ei 0 - O 0
<br /> d. CLAMPS FOR ATTACHMENT TO STEEL STRUCTURAL ELEMENTS. 3. CABLE TRAY SUPPORTS AND CONNECTORS. D. LOAD CENTERS: Z Q Q
<br /> e. ALL STEEL, SPRINGHEAD TOGGLE BOLTS. D. WARNING SIGNS: 1-1/2-INCH- (40-MM-) HIGH, BLACK LETTERS ON YELLOW 1. MAINS: LUGS ONLY. e. SHUNT TRIP. Q
<br /> f. THREADED HANGER RODS. BACKGROUND WITH LEGEND "WARNING! NOT TO BE USED AS WALKWAY, LADDER, OR �
<br /> 2. BRANCH CIRCUIT BREAKERS: PLUG-IN. f. UNDERVOLTAGE TRIP: 35 TO 75 PERCENT OF RATED VOLTAGE WITHOUT U U N
<br /> B. FABRICATED METAL EQUIPMENT SUPPORT ASSEMBLIES: WELDED OR BOLTED SUPPORT FOR LADDERS OR PERSONNEL". O U
<br /> 3. DOORS: CONCEALED HINGE. INTENTIONAL TIME DELAY. W �r nn W
<br /> STEEL SHAPES. 4. CONDUCTOR CONNECTORS: MECHANICAL TYPE. AUXILIARY CONTACTS:TWO SPDT SWITCHES. V O z
<br /> 1.3 SOURCE QUALITY CONTROL 9 O O
<br /> END OF SECTION 260529 A. TESTED ACCORDING TO NEMA FG 1. E. DISCONNECTING AND OVERCS-THER RRENTALMA PROTECTIVE DEVICES: h. ALARM SWITCH: ONE NO CONTACT. a O <
<br /> 1. CIRCUIT BREAKERS-THERMAL-MAGNETIC TYPES. i. KEY INTERLOCK KIT.
<br /> END OF SECTION 260536 2. GFI CIRCUIT BREAKERS: RATED FOR PERSONNEL. j. ZONE-SELECTIVE INTERLOCKING: INTEGRAL WITH ELECTRONIC TRIP.
<br /> 3. AFCI CIRCUIT BREAKERS: AS REQUIRED BY CODE.
<br /> 4. OPTIONS AND TYPES AS NEEDED. k. ELECTRICAL OPERATOR. STORE #: 9287
<br /> F. IDENTIFICATION: I. ACCESSORY CONTROL POWER. PROJECT #: 23544-077
<br /> ELECTRICAL 1. PANELBOARD LABELS: MANUFACTURER'S NAME AND TRADEMARK, VOLTAGE, D. MOLDED-CASE SWITCHES:
<br /> AMPERAGE, NUMBER OF PHASES, ARC FLASH HAZARD, AND NUMBER OF POLES 1. MCCB WITH FIXED, HIGH-SET INSTANTANEOUS TRIP ONLY, AND SHORT-CIRCUIT ISSUE DATE: 03/12/2021
<br /> SHALL BE LOCATED ON THE INTERIOR OF THE PANELBOARD DOOR. WITHSTAND RATING EQUAL TO EQUIVALENT BREAKER FRAME SIZE
<br /> SECTION 260544-SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING 2. BREAKER LABELS: FACEPLATE SHALL LIST CURRENT RATING, UL AND IEC INTERRUPTING RATING. SR. DESIGN MANAGER: JESSICA RAMOS
<br /> 1.1 MATERIALS CERTIFICATION STANDARDS, AND AIC RATING. 2. FEATURES AND ACCESSORIES: DESIGN MANAGER: HT
<br /> A. SLEEVES: 3. CIRCUIT DIRECTORY: DIRECTORY CARD INSIDE PANELBOARD DOOR, MOUNTED a. LUGS: MECHANICAL. CHECKED BY: TG
<br /> 1. SCHEDULE 40 STEEL PIPE. IN METAL FRAME WITH TRANSPARENT PROTECTIVE COVER b. GROUND-FAULT PROTECTION: REMOTE-MOUNTED AND POWERED TYPE.
<br /> G. ACCESSORIES: c. SHUNT TRIP.
<br /> 2. CAST-IRON PIPE. 1. ACCESSORY SET INCLUDING TOOLS. d. UNDERVOLTAGE TRIP: 35 TO 75 PERCENT OF RATED VOLTAGE WITHOUT Revision Schedule
<br /> 3. GALVANIZED-STEEL SHEET FOR CONDUITS PENETRATING NON-FIRE-RATED 2. PORTABLE TEST SET: FOR TESTING FUNCTIONS OF SOLID-STATE TRIP DEVICES INTENTIONAL TIME DELAY.
<br /> GYPSUM-BOARD ASSEMBLIES. e. AUXILIARY CONTACTS:TWO SPDT SWITCHES
<br /> WITHOUT REMOVING FROM PANELBOARD. Rev Date By Description
<br /> 4. MOLDED-PE OR-PP PIPE.
<br /> f. ALARM SWITCH: ONE NO CONTACT. 03/12/21 ACIES PERMIT SET
<br /> 5. GALVANIZED-STEEL SHEET FOR RECTANGULAR OPENINGS. 1.3 FIELD QUALITY CONTROL
<br /> g. KEY INTERLOCK KIT.
<br /> B. SLEEVE-SEALS: A. TESTING: BY CONTRACTOR. h. ZONE-SELECTIVE INTERLOCKING: INTEGRAL WITH REMOTE GROUND-FAULT
<br /> 1. EPDM RUBBER SEALING ELEMENTS. TRIP UNIT.
<br /> 2. CARBON-STEEL PRESSURE PLATES. END OF SECTION 262416 i. ELECTRICAL OPERATOR.
<br /> 3. CARBON-STEEL, WITH CORROSION-RESISTANT COATING, j. ACCESSORY CONTROL POWER.
<br /> CONNECTING BOLTS AND NUTS. E. ENCLOSURES:
<br /> C.D. SILICONE HYDRAULSEALANIC-CEMENT
<br /> GROUT. ELECTRICAL 1. INDOOR, DRY AND CLEAN LOCATIONS: NEMA 250, TYPE 1. SHEET TITLE:
<br /> 2. OUTDOOR LOCATIONS: NEMA 250, TYPE 3R. ELECTRICAL OUTLINE
<br /> 1. SINGLE-COMPONENT, SILICONE-BASED, NEUTRAL-CURING ELASTOMERIC
<br /> SEALANT. SECTION 262713 - ELECTRICITY METERING 1.2 FIELD QUALITY CONTROL
<br /> 2. MULTICOMPONENT, SILICONE-BASED LIQUID ELASTOMERIC NONSHRINKING 1.1 EQUIPMENT FOR ELECTRICITY METERING BY UTILITY COMPANY A. TESTING: BY CONTRACTOR. SPECIFICATIONS
<br /> FOAM. A. UTILITY-COMPANY-COMPLIANT CURRENT-TRANSFORMER CABINETS: COMPLY WITH
<br /> 3. VOC CONTENT OF 250 G/L OR LESS. REQUIREMENTS OF ELECTRICAL-POWER UTILITY COMPANY. 1.3 ADJUSTING SCALE:
<br /> END OF SECTION 260544 B. METER SOCKETS: COMPLY WITH REQUIREMENTS OF ELECTRICAL-POWER UTILITY A. SET FIELD-ADJUSTABLE CIRCUIT-BREAKER TRIP RANGES.
<br /> COMPANY. SHEET NUMBER:
<br /> END OF SECTION 262816 E-002
<br /> END OF SECTION 262713
<br />
|