GENERAL NOTE POWER PLAN NOTES SHEET NOTES <br /> 1. REUSE EXISTING ELECTRICAL PANELS AND RECONNECT THE A. FURNISH AND INSTALL A COMPLETE AND OPERATING SYSTEM. O PROVIDE CONNECTION FOR POS BANK. FIELD COORDINATE FOR <br /> RELOCATED LOADS AS REQUIRED. IF NEW LOADS ARE ADDED, ALL ITEMS ARE NOT NECESSARILY SHOWN. 1 <br /> USE AVAILABLE SPARE CIRCUITS. EXACT LOCATION AND REQUIREMENT. EXTEND EXISTING WIRING <br /> B. ELECTRICAL CONTRACTOR RESPONSIBLE FOR SITE FOR PREVIOUSLY USED THE SAME TYPE OF EQUIPMENT IN :� <br /> 2. FIELD VERIFY THE RATINGS OF THE EXISTING PANELS AND INVESTIGATION PRIOR TO START OF WORK TO REVEAL FULL EXISTING DEMO LOCATION TO THIS NEW LOCATION. CONNECT <br /> AVAILABLE SPARE CAPACITIES. IF NEW LOADS ARE ADDED TO SCOPE OF WORK. TO CIRCUIT AS SHOWN. <br /> THE PANEL DO NOT EXCEED THE RATING OF THE PANEL <br /> INCLUDING THE RATINGS OF THE UPSTREAM SERVING C. DIMENSIONS ARE TO FINISH FACE UNLESS OTHERWISE NOTED. O PHONE LINE. FIELD COORDINATE EXACT LOCATION. <br /> FEEDER AND CIRCUIT BREAKER. <br /> 3. ALL CIRCUIT NUMBERS SHOWN HERE ARE BASED ON D. REFER <br /> MOUNTING ODETAIL SHEETS H HEIGHTS OF ELECCTREXACT LOCATIONS RICAL DEVICES. EXACT <br /> O EXAOVIDE CT LOCATIONA DNFOR REGISTER. FIELD REQU REQUIREMENT. EXTEND EXISTING WIRING 0 <br /> PROVIDEDRECORD DRAWING. IF THE ACTUAL EXISTING CIRCUIT FOR PREVIOUSLY USED THE SAME TYPE OF EQUIPMENT IN <br /> NUMBERS ARE DIFFERENT THAN THE ONES SHOWN HERE, USE E. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR EXISTING DEMO LOCATION TO THIS NEW LOCATION. ©2020 STARBUCKS COFFEE COMPANY <br /> THE ACTUAL NUMBERS AND PROVIDE UPDATED TYPEWRITTEN CONFIRMING ALL VOLTAGE REQUIREMENTS ON ALL <br /> SCHEDULE IN ALL PANELS USED IN THIS PROJECT. EXISTING LECTRICAL PANEL TEMAIN. FIELD VERIFY EXACT <br /> MAYIBE NEEDED OR PIRO PER O ERAOTIION OF THE ORMERS AS O LOCAT ONE PROVIDE UPDATEDOTYR EWRITT N SCHEDULE UPON STA R B V C KS° <br /> EQUIPMENT.ALL ARE NOT NECESSARILY INDICATED. COMPLETION OF THIS PROJECT. SEE PANEL SCHEDULE ON 2401 UTAH AVENUE SOUTH <br /> F. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH SHEET E-601. MAINTAIN 36" CLEARANCE IN FRONT OF PANELS. SEATTLE, WASHINGTON 98134 <br /> PLUMBING AND HEATING, VENTILATING,AND AIR O EXISTING POS TO BE RELOCATED HERE AND RE-CONNECTED TO (206) 318-1575 <br /> CONDITIONING (HVAC)CONTRACTORS FOR ANY ADDITIONAL EXISTING CIRCUIT PREVIOUSLY USED FOR SAME EQUIPMENT. <br /> EQUIPMENT NEEDING POWER. O THESE DRAWINGS AND THE PROJECT MANUAL ALL 120V RECEPTACLES IN WORKROOM AND BAR AREA SHALL BE ARE CONFIDENTIAL AND SHALL REMAIN THE <br /> G. ANY EQUIPMENT NOTED AS `FUTURE' SHALL BE PROVIDED GFCI RATED. AND ALL SINGLE PHASE RECEPTACLES RATED 150 SOLE PROPERTY OF STARBUCKS <br /> WITH APPROPRIATE RECEPTACLES AND WIRING TO ENABLE VOLTS TO GROUND OR LESS, 50A OR LESS AND THREE PHASE CORPORATION, WHICH IS THE OWNER OF THE <br /> FUTURE OPERATION. RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 100A OR COPYRIGHT IN THIS WORK. THEY SHALL NOT <br /> LESS INSTALLED IN THE FOLLOWING LOCATIONS SHALL HAVE COOREPRODUCED (IN WHOLE OR IN PART), <br /> H. GROUND FAULT CIRCUIT INTERRUPTER (GFCI) BREAKERS (NOT GROUND FAULT CIRCUIT INTERRUPTER PROTECTION FOR BE SHARED WITH THIRD PARTIES OR USED IN ANY <br /> RECEPTACLES) SHALL BE UTILIZED WHERE REQUIRED BY PERSONNEL. MANNER ON OTHER PROJECTS OR <br /> CODE AND AT ANY FLOOR BOXES. PROVIDE DEDICATED EXTENSIONS TO THIS PROJECT WITHOUT THE <br /> NEUTRAL WIRE FOR ALL THESE CIRCUITS. O7 EXISTING GRINDER/DIGITAL SCALE TO BE RELOCATED HERE. PRIOR WRITTEN CONSENT OF STARBUCKS <br /> I. DISCONNECT AND REMOVE EXISTING ELECTRICAL DEVICES FIELD COORDINATE EXACT LOCATION AND REQUIREMENT. IF CORPORATION. THESE DRAWINGS AND <br /> FOR EXISTING EQUIPMENT TO BE REMOVED. REROUTE POSSIBLE, EXTEND THE EXISTING CIRCUIT PREVIOUSLY USED SPECIFICATIONS ARE INTENDED TO EXPRESS <br /> CONDUIT AND CONDUCTORS AROUN WALLS AND CEILING FOR THE SAME LOAD IN THIS AREA. IF NO SUCH CIRCUIT IS DESIGN INTENT FOR A PROTOTYPICAL <br /> AFFECTED BY REMODEL SO THAT DOWN STEAM DEVICES TO AVAILABLE, PROVIDE NEW CONNECTION TO IT. STARBUCKS STORE (WHICH IS SUBJECT TO <br /> REMAIN STAY POWERED. REMOVE PORTIONS NO LONGER CHANGE AT ANYTIME)AND DO NOT REFLECT <br /> REQUIRED BACK TO NEAREST JUNCTION BOX OR TO SOURCE. O EXISTING BREWER SOFT HEAT DUAL TO BE RELOCATED HERE. ACTUAL SITE CONDITIONS. NEITHER PARTY <br /> TRACE ALL CIRCUITS IN THE AFFECTED AREAS PRIOR TO FIELD COORDINATE EXACT LOCATION AND REQUIREMENT. IF SHALL HAVE ANY OBLIGATION NOR LIABILITY TO <br /> CONSTRUCTION AND RE-LABEL PANELS ACCORDINGLY. POSSIBLE, EXTEND THE EXISTING CIRCUIT PREVIOUSLY USED THE OTHER (EXCEPT STATED ABOVE) UNTIL A <br /> FOR THE SAME LOAD IN THIS AREA. IF NO SUCH CIRCUIT IS WRITTEN AGREEMENT IS FULLY EXECUTED BY <br /> J. WORKING CLEARANCES SHALL BE MAINTAINED AND ARE AVAILABLE, PROVIDE NEW CONNECTION TO IT. I BOTH PARTIES. <br /> SUBJECT TO FIELD VERIFICATION PER NEC 110.16. <br /> O EXISTING BREWER SOFT HEAT SERVER/SINGLE WARMING STARBUCKS TEMPLATE VERSION: i2020.10.23 <br /> K. GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL STAND TO BE RELOCATED HERE. FIELD COORDINATE EXACT <br /> BEINSTALLED IN KITCHENS PER NEC 210.8(B)(2). SUBJECT TO LOCATION AND REQUIREMENT. IF POSSIBLE, EXTEND THE <br /> FIELD VERIFICATION. EXISTING CIRCUIT PREVIOUSLY USED FOR THE SAME LOAD IN <br /> L. GROUND-FAULT CIRCUIT-INTERRUPTER SHALL BE INSTALLED THIS AREA. IF NO SUCH CIRCUIT IS AVAILABLE, PROVIDE NEW architecture <br /> IN A READILY ACCESSIBLE LOCATION PER NEC 210.8. SUBJECT CONNECTION TO IT. and interiors <br /> TO FIELD VERIFICATION. EXISTING UNDERCOUNTER FRIDGE TO BE RELOCATED HERE. <br /> 10 <br /> M. SIGNS AND OUTLINE LIGHTING SYSTEM EQUIPMENT FOR WET FIELD COORDINATE EXACT LOCATION AND REQUIREMENT. IF <br /> LOCATION USE, OTHER THAN LISTED WATERTIGHT TYPE, POSSIBLE, EXTEND THE EXISTING CIRCUIT PREVIOUSLY USED 5858 Wilshire Blvd #200 T: 323.954.8996 <br /> SHALL BE WEATHERPROOF AND HAVE DRAIN HOLES, AS FOR THE SAME LOAD IN THIS AREA. IF NO SUCH CIRCUIT IS <br /> NECESSARY, IN ACCORDANCE WITH THE FOLLOWING: DRAIN AVAILABLE, PROVIDE NEW CONNECTION TO IT. Los Angeles, CA 90036 F: 323.954.8965 <br /> HOLES SHALL NOT BE LARGER THAN 1/2 INCH OR SMALLER www.valerioinc.com * info@valerioinc.com <br /> /4 <br /> THAN ' INCH. EVERY LOW POINT OR ISOLATED SECTION 11 EXISTING FOOD CASE TO BE RELOCATED HERE. FIELD <br /> SHALL HAVE AT LEAST ONE DRAIN HOLE; DRAIN HOLES SHALL COORDINATE EXACT LOCATION AND REQUIREMENT. IF POSSIBLE, <br /> HAVE NO EXTERNAL OBSTRUCTIONS. EXTEND THE EXISTING CIRCUIT PREVIOUSLY USED FOR THE <br /> SAME LOAD IN THIS AREA. IF NO SUCH CIRCUIT IS AVAILABLE, <br /> N. CALIFORNIA ELECTRICAL CODE REQUIRES THE SERVICE PROVIDE NEW CONNECTION TO IT. FESS <br /> r��pQft� aNq Iii <br /> O EQUIPMENT'S MAIN DISCONNECT SWITCH AND FUSE, OR THE ACIES rrr����tSLAV 2 C9`�yitZi <br /> � PROVIDE CONNECTION FOR NEW FRIDGE NITRO. FIELD <br /> CIRCUIT BREAKER, TO BE RATED AT THE AVAILABLE <br /> SHORT-CIRCUIT CURRENT VALUE. ALL NEW NON-RESIDENTIAL, COORDINATE EXACT LOCATION AND REQUIREMENT. IF POSSIBLE, ENGINEERING 3U <br /> INDUSTRIAL AND MANUFACTURING ARE SUPPLIED BY AN EXTEND THE EXISTING CIRCUIT PREVIOUSLY USED FOR THE 400 N McCarthy Blvd. r <br /> CA 95035itas <br /> Mil <br /> Suite 250, p , <br /> INDIVIDUAL SERVICE DROP OR LATERAL RATED AT 225 AMPS SAME LOAD IN THIS AREA. IF NO SUCH CIRCUIT IS AVAILABLE, Su <br /> OR MORE ARE REQUIRED TO HAVE A FAULT CURRENT LETTER PROVIDE NEW CONNECTION AND CONNECT TO CIRCUIT AS p522-5255 <br /> ( <br /> x 408)522-5260 CA <br /> 222111g1�fCTR�GO����rr <br /> E <br /> PROVIDED BY PG&E OR THE ELECTRICAL SERVICE PROVIDER SHOWN. info@acies .net tttti�,ti�ti^� <br /> Copyright©2021 <br /> O. EQUIPMENT INTENDED TO BREAK CURRENT AT FAULT LEVELS 13 EXISTING ESPRESSO MACHINE TO BE RELOCATED HERE. FIELD <br /> 11 SHALL HAVE AN INTERRUPTING RATING SUFFICIENT FOR THE COORDINATE EXACT LOCATION AND REQUIREMENT. IF POSSIBLE, <br /> SYSTEM VOLTAGE AND THE CURRENT WHICH IS AVAILABLE AT EXTEND THE EXISTING CIRCUIT PREVIOUSLY USED FOR THE <br /> THE LINE TERMINALS OF THE EQUIPMENT. THERE ARE TWO SAME LOAD IN THIS AREA. IF NO SUCH CIRCUIT IS AVAILABLE, <br /> WAYS TO SATISFY THE CODE REQUIREMENT: EITHER SERIES PROVIDE NEW CONNECTION TO IT. <br /> ■ RATED OR FULLY RATED. ANY NEW BREAKERS OR <br /> SUB-PANELS MUST MEET THIS REQUIREMENT. <9> PROVIDE CONNECTION FOR NEW HOT WATER DISPENSER. FIELD <br /> O3 ® COORDINATE EXACT LOCATION AND REQUIREMENT. IF POSSIBLE, <br /> JF1 P. GC TO NOTIFY SBUX CM + DM IF THERE ARE ANY (E) FLOOR EXTEND THE EXISTING CIRCUIT PREVIOUSLY USED FOR THE <br /> OUTLETS THAT NEED TO BE RELOCATED OR REMOVED. SAME LOAD IN THIS AREA. IF NO SUCH CIRCUIT IS AVAILABLE, <br /> 2 Q. EQUIPMENT REQUIRES CONNECTION TO THE BUILDING PROVIDE NEW CONNECTION AND CONNECT TO CIRCUIT AS <br /> ELECTRICAL SYSTEM. FURNISH AND INSTALL ALL NECESSARY SHOWN. <br /> CONDUIT, WIRE, CONNECTIONS, RECEPTACLES AND 15 PROVIDE CONNECTION FOR NEW WARMING OVEN. FIELD <br /> OVERCURRENT PROTECTION NECESSARY TO ENSURE THE COORDINATE EXACT LOCATION AND REQUIREMENT. IF POSSIBLE, <br /> ■ 5 ® EQUIPMENT FUNCTIONS PROPERLY AND COMPLIES WITH ALL EXTEND THE EXISTING CIRCUIT PREVIOUSLY USED FOR THE Q <br /> 7 1 APPLICABLE LOCAL AND NATIONAL CODES. COORDINATE SAME LOAD IN THIS AREA. IF NO SUCH CIRCUIT IS AVAILABLE, <br /> IC) EQUIPMENT REQUIREMENTS WITH MANUFACTURER CUT PROVIDE NEW CONNECTION AND CONNECT TO CIRCUIT AS <br /> SHEET PRIOR TO ROUGH-IN. SHOWN. -r-- <br /> Z <br /> FA-1 ,a]I I ii�8 <br /> R. ALL FRONT BAR J-BOXES AND OUTLETS SHALL BE SURFACE 16 PROVIDE CONNECTION FOR FUTURE MOBILE ORDER, PAY& � � Lr) <br /> O <br /> MOUNTED. PROVIDE CONDUITS AS NEEDED AND ONE (1) PRINT LABELER. FIELD COORDINATE EXACT LOCATION AND ! , <br /> 9 E 20032 15 ADDITIONAL SPARE CONDUIT BETWEEN ALL J-BOXES FOR REQUIREMENT. LU <br /> 0- Q U <br /> FUTURE ELECTRICAL REQUIREMENTS. ALL J-BOXES SHALL BEU z <br /> E 20010 12 <br /> B-(24,28) � POSITIONED TO AVOID OBSTRUCTION OF ANY EQUIPMENT O PROVIDE CONNECTION TO DIGITAL MENU BOARD. FIELD J � _ <br /> 2#10+1#10G 0 �� 1 SUCH AS REFRIGERATORS AND DISHWASHERS. 17 COORDINATE EXACT LOCATION. W <br /> 4"C 10 6 B-36 e LLI z � <br /> S. REFERENCE LANDLORD WORK LETTER FOR DIVISION OF _ <br /> ELECTRICAL SCOPE OF WORK AND COORDINATE WITH Q �/ O <br /> B-(28,30) VE 1A STARBUCKS CONSTRUCTION MANAGER. z Q <br /> 2#10+1#10G 1 O H H ~ O <br /> 3/4"C. A-(2,4) T. DATA CABLING LOCATED ABOVE HEAD SHALL BE PLENUM. U <br /> 2#8+1#10G O �I� O C:)O z <br /> 16 6 3/4"C. U. DATA CABLING LOCATED UNDERGROUND SHALL BE RATED `JQD <br /> 0 <br /> FOR BELOW GROUND USE. 0 0Q <br /> 4 PANEL..B.' 1 (� 0 U) <br /> PANEL"A" i A E 19742 d13 <br /> (2 ��J A <br /> STORE #: 9287 <br /> EIL 10 22,24) 4A PROJECT #: 23544-077 <br /> -( I <br /> 0 P 15749 14 <br /> ISSUE DATE: 03/12/2021 <br /> SR. DESIGN MANAGER: JESSICA RAMOS <br /> A-(6,8)LL=1 ap 16 DESIGN MANAGER: HT <br /> +1#10G <br /> CHECKED BY: TG <br /> r <br /> 3/4" <br /> O A Revision Schedule <br /> (2 E 19742 13 <br /> Rev Date By Description <br /> 03/12/21 ACIES PERMIT SET <br /> - 6 <br /> SHEET TITLE: <br /> ELECTRICAL <br /> POWER DESIGN <br /> SCALE: <br /> Power Plan SHEET NUMBER: <br /> 1 Soa e 1/4" = 1'-o" E-103 <br />