Laserfiche WebLink
14749 N Thronton Rd, Lodi Record ID PR0519127 <br /> 12/2/2019 Hazardous Waste <br /> Photo 5: The tank assessment observed during the inspection was last done on 1/28/2010. No current reassessment was available for review and the <br /> mana er, Francisco Avila, was not sure if another one had been done. <br /> I �` M i� <br /> I e Smith Engineering;, Inc. <br /> 1'•0- Box 611 Lodi,CA 95240 <br /> 209-334-2332 Fax 209-334-0102 <br /> 1-2s-10 <br /> II 3 B's Truck&Auto plaza <br /> 14749 N.Thornton I'd <br /> Lodi,Ca 95242 <br /> Re:Hazardous Wastc Tank Assessment For: <br /> Auto Plaza <br /> 14749 N.Thorn,on Rd <br /> Lodi,Ca 95242 <br /> An assessment has been performed upon the waste oil storage system,at the above <br /> referenced location vi order to determine if it meets the requirements of California Title <br /> i 22 requirements for l.azardous waste storage. <br /> Description• <br /> 3 B's Truck&Auto:'laza provides multiple services for travelers on interstate 5. One of <br /> the services provided is oil change for primarily large trucks. There is a service pit that is <br /> 4'-0"wide,30'-0"to-ig and 4'-0"deep for the mechanics to access the underside of the <br /> vehicles. There is a moveable pan that collects the waste oil that is easily adjusted to be <br /> directly below the ve.Acle oil plug. This pan has a steel reinforced flexible rubber suction <br /> pump that is mountec.on top of the storage tank. The suction line is either flexible rubber <br /> hose where fittings have containment or copper pipe with soldered connections. The <br /> service pit provides c:)ntainment for fittings at the moveable pan. There are 10 GA steel <br /> containment pans at toe pump and at the discharge connection. The tank is a steel tank <br /> with integral secondary containment with leak detection sensors and an overfill alarm. <br /> The entire system is located inside of a building with approximately 20'-0"between <br /> collection pan and stc rage tank. Modifications have been performed for this system to <br /> meet Title 22 requirements. <br /> Tank Assessment er 22 CCR 66295.192 <br /> 1} Tank �?aa�°n' <br /> Above ground"lube cube"steel tank with integral secondary containment,and <br /> approximately 1000 gallon capacity. <br /> la) Material Stora e; <br /> Tank is used to stare waste ail. <br /> Specific Gravity==.85 <br /> Densis 531b/cf <br /> John Alaniz, REHS Page 5 of 12 <br />