Laserfiche WebLink
Equipment Service Checklist <br /> ENE:R6Y SYSTEMS Customer: BNSF-Stockton WO Number: 77807 <br /> r D W C h 5 S T C V v <br /> Address: 6540 S. Austin Road Site: East Yard Bldg#7 <br /> Code: <br /> Location: Stockton, CA 95215 ServicedBy: Koncewicz, Bobby <br /> Generator Engine Automatic Transfer Switch <br /> Make: Generac Make: New Holland Make: Generac <br /> Model: 20A02070-S Model: Model: 20A-02070-W <br /> Spec: Spec: Spec: <br /> SN: 2056970 SN: SN: 27157 <br /> Voltage: 277/480 30 Hours: 300 Voltage: 277/480 Amps: 400 <br /> Amps: 150 KW: 100 9V Bat.: <br /> Battery System Fuel System Misc <br /> Cables: ok Filters: ok Belts: ok <br /> Level: ok Lift Pump: ok Hoses: ok <br /> Spec Gravity: ok Day Tank Level: 95% Fluid Leaks: ok <br /> Charger: ok Governor: ok Air Filters: ok <br /> Corrosion: ok Filter 1#: Exh System: ok <br /> Cap Test: ok Filter 2#: Cleanliness: ok <br /> Size: 4d vhd Ignition System LPG/NAT Gas <br /> Qty: 1 Spark Plugs: n/a Regulators: n/a <br /> Date July-2017 Plug Wires: n/a Solenoids: n/a <br /> Lube System Dist/Mag: n/a Press Switch: n/a <br /> Oil: replaced-20 qts Carb: n/a Carb: n/a <br /> Filters: ok Timing: n/a Tanks: n/a <br /> Filter 1#: b2-replaced Cooling System Functional Test <br /> Filter 2#: n/a Filters: ok Oil Press(PSI): 65 <br /> Gen and Control PNL Radiators: ok Water Temp(°F): 160 <br /> Meters: ok Block Heater: ok Batt Chg Volts: 13.5 Amps: 0 <br /> Eng Gages: ok Anti-Freeze: ok Frequency(Hz): 60.0 <br /> Lamps: ok Water Pump: ok Volt L1: 481 L2 480 L3 481 <br /> Exciter: ok Fan: ok Amps L1: L2 L3 <br /> Stator Main: ok Pressure Test: ok Trns.Switch Aut: yes <br /> Rotor Main: ok Gen Auto: yes <br /> Comments <br /> Perform inspection on generator and transfer switch. Check control panel for any active alarms. Found none.Turn off. Check <br /> all levels, connections, block heater, belts, hoses and battery. Check and test radiator,-ok! Check and test battery,-ok! <br /> Perform pm service-change oil, oil filter,fuel filters, and clean battery. <br /> Test ran generator- no load-check for leaks and output voltage. Generator performs as it should with no problems. All checks <br /> ok! Generator left in auto position. <br /> Recommendations <br /> Ultra Low Sulfur (CARB) Diesel Fuel 5/9/2018 <br /> Purchased From: n/a Technician Signature Date <br />