Laserfiche WebLink
SAN TOA ( UIN <br />L�l� J L�t,[V11\ <br />Department of <br />Page of <br />HOUSEKEEPING <br />2 2 <br />GENERAL HOSPITAL <br />Policy/Procedure <br />Effective Date <br />Date Replaces <br />7.11A <br />7/02 <br />1/96 <br />�f� pp��'';;cc pp e���,`,,r� <br />TithPERATIN�(PrRo�E%bRES FOR PROCESSING INFECTIOUS WASTE <br />8. At the end of the cycle, the operator will check the recorder chart and verify that the machine has <br />actually achieved 275 degrees Fahrenheit for 45 minutes. After verification initial the chart and the <br />date for an on-going record of each cycle. If the chart indicates that the time or temperature had not <br />not been achieved, the operator must rerun the cycle and write "rerun" on the chart. Then complete <br />the following procedures: <br />a. Unlatch the safety from the locking ring and rotate the locking ring into the opening position. <br />b. Using gloves provided, carefully open the door. Lower the ramp and remove the carts. Dump <br />the carts as you would ordinary trash. The autoclave is now ready for the next load. <br />c. When a load fails or needs to be rerun, a department supervisor will be notified by calling 468-6893. <br />d. The supervisor will review and initial the steam sterilizer chart corresponding with the failed or rerun load. <br />e. The supervisor will ensure that it is clearly documented why a load did not pass and the results of the rerun. <br />AUTHORS: Housekeeping <br />Item N 575 Hosp. 3407 (10/96) <br />