Laserfiche WebLink
April 7, 2009 Lab ID : STK0932169 <br /> San Joaquin County Solid Waste Customer : 3-2956 <br /> Organic QC <br /> 03/09/2009:202484 All preparation quality controls are within established criteria,except: <br /> 5030B The following note applies to 2-Hexanone,4-Methyl-2-pentanone(MIBK): <br /> 210 The method blank was positive.However,samples reported were either ten times greater than the blank <br /> concentration or non detect and accepted. <br /> 5310C 03/12/2009:203331 All analysis quality controls are within established criteria. <br /> 03/12/2009:202647 All preparation quality controls are within established criteria. <br /> 03/11/2009:202529 All preparation quality controls are within established criteria,except: <br /> 815013 The following note applies to Dalapon,Dinoseb,Picloram: <br /> 435 Sample matrix may be affecting this analyte.Data was accepted based on the LCS or CCV recovery. <br /> 03/19/2009:203488 All analysis quality controls are within established criteria,except: <br /> 8151A The following note applies to 2,4-D,2,4-DB,2,4-DCAA,2,4,5-T,Dichlorprop,Picloram: <br /> 360 CCV above Acceptance Range(AR).Samples which were non detect for this analyte were accepted. <br /> 03/09/2009:203060 All analysis quality controls are within established criteria,except: <br /> 8260B The following note applies to Methyl tert-Butyl Ether: <br /> 360 CCV above Acceptance Range(AR). Samples which were non detect for this analyte were accepted. <br /> 03/10/2009:203153 All analysis quality controls are within established criteria. <br /> Inorganic-Wet Chemistry QC <br /> 2.13013 03/05/2009:202963 All analysis quality controls are within established criteria. <br /> 03/05/2009:202399 All preparation quality controls are within established criteria. <br /> 2320B 03/11/2009:203244 All analysis quality controls are within established criteria. <br /> 03/12/2009:203245 All analysis quality controls are within established criteria. <br /> 03/11/2009:202568 All preparation quality controls are within established criteria. <br /> 2510B 03/06/2009:202956 All analysis quality controls are within established criteria. <br /> 03/06/2009:202386 All preparation quality controls are within established criteria. <br /> 2540 C 03/06/2009:202411 All preparation quality controls are within established criteria. <br /> 300.0 03/05/2009:202942 All analysis quality controls are within established criteria. <br /> 03/05/2009:202379 All preparation quality controls are within established criteria. <br /> Page 2 of 27 <br />