Laserfiche WebLink
TABLE 3 <br /> FACILITY-WIDE POTENTIAL TO EMIT EMISSION SOURCE ESTIMATES <br /> FOOTHILL LANDFILL <br /> LINDEN,CALIFORNIA <br /> Criteria Pollutant Emissions <br /> NOx CO* PM-10 SOx VOCs* <br /> E ui ment Ib/hr lbs/da tons/ r Ib/hr lbs/da tons/yr Ib/hr lbs/da tons/yr Whir lbs/day tons/yr Ib/hr lbs/da tons/ r <br /> Future <br /> LFGTE Facili Flare 0.23 5.55 1.01 1.13 27.07 4.94 0.28 6.77 1.24 0.28 6.76 1.23 0.61 14.61 2.67 <br /> LFGTE Facility(Engine No. 1 1.00 23.91 4.36 11.95 286.86 52.35 0.66 15.94 2.91 1.41 33.85 6.18 0.91 21.88 3.99 <br /> LFGTE Facility(Engine No.2 1.00 23.91 4.36 11.95 286.86 52.35 0.66 15.94 2.91 1.41 33.85 6.18 0.91 21.88 3.99 <br /> Current Total 2.22 1 53.36 1 9.74 25.03 1 600.80 1 109.65 1 1.61 1 38.64 7.05 3.10 74.46 13.59 2.43 58.38 10.65 <br /> Notes: <br /> NOx= Nitrogen Oxides <br /> CO = Carbon Monoxide <br /> PM-10 = Particulate Matter less than 10 microns <br /> SOx = Sulfur Oxides <br /> VOCs=Volatile Organic Compounds <br /> PTE=Potential to Emit <br /> *CO will be capped at 99.99 tpy,VOCs will be capped at 9.99 tpy,and SOx will be capped at 17.0 tpy <br />