Laserfiche WebLink
C7 <br />,� 13aiaServite� - Secure ��►��ro�t»n��rl-�+�ta': f <br />Foothill, - <br />LANDFILL GAS MONITORING <br />di li <br />DATE: 08/07/2012 <br />TECHNICIAN: Mcalmes <br />TEMPERATURE: 94 <br />BAR. PRESSURE: 29.70 <br />WEATHER: Calm <br />WIND DIRECTION: West SPEED: 2 <br />SITE ID: 1,473 <br />JOB NO.: <br />Pre -monitoring Calibration Precision Check <br />Procedure: Calibrate the instrument. Make a total of three measurements by alternating zero air and the <br />calibration gas. Record the readings and calculate the average algebraic difference between the instrument <br />reading and the calibration gas as a percentage. The calibration precision must be less than or equal to 2% of <br />the calibration gas value. <br />Instrument Type: GEM 2000 Instrument Serial No. 8049 <br />Calibration Gas: <br />CH4 % <br />CO2 % <br />02% <br />15.0 <br />15.0 <br />4.0 <br />Pre -monitoring Calibration Check <br />Time <br />CH4 % <br />CO2 % <br />02% <br />12:45:00 PM T <br />15.0 <br />15.0 <br />4.0 <br />Post -monitoring Calibration Check <br />Time <br />CH4 % CO2 % <br />02% <br />03:45:00 PM <br />15.0 15.0 <br />4.0 <br />COMMENT 1: <br />COMMENT 2: <br />REVIEWED BY: DATE: <br />