� �3 •:-" r^x`*u k aY.°x, �. -� :.c �: .. ,3r�' "�, � '�",�a" �;t � `b -s v ; <br /> `zit" <br /> T27CCR 20939(b)(1)-Sub-surface Landfill Gas Control Systems—The facility has experienced 5 subsurface landfill fires.Four of the fires occurred in this year.The <br /> fires are all located along the toe of the slope.The latest fire occurred a long the western toe of the old Forward Inc portion of the landfill. The fin:occurred along the <br /> horizontal collector.The facility operator indicated that they would place soil over the area and monitor it The operator provided a copy of the facility response plan the <br /> pertained to sub-surface landfill fires.It is currently under review.It appears that the landfill gas system is over pulling and creating fires that erupt below the surface of <br /> the landfll. The facility shall review and evaluate the gas control system to determine what can be done to prevent further instances of sub-surface landfill fires.The <br /> site operator is currently working with the CIWMB to resolve the issue. <br /> Notes: <br /> 1.The tarps used as daly'cover were not balasted to prevent the tarps from being removed during high winds. <br /> Properly weigh down the tarps each night <br /> 2.The daily cover consisted of tarps,TASW,soil. <br /> 3.The perimeter gas probes were monitored using a Landtec Gem 500 field screening device,during the inspection,The <br /> following was noted: <br /> SGS (S)(1)(D)0.0%CH4 <br /> SG11 (S)0.2%CH4(1)1.7%CH4(D)0.0% <br /> SG12(S)2.1%CH4(1)0.0%CH4(D)0.5% <br /> 4.The following Areas of Concern listed on the previous inspection report were resolved: <br /> a.T27CCR 20820-Drainage and Erosion Control <br /> b.T27CCR 20921 (a)(2)-Explosive Gas Control <br />