p <br /> meter to sound. This point is usually clearly visible on the probe. If it is not visible it should <br /> located by dipping the probe into a water container where the contact'can be clearly seen, Lhen l. <br /> marked. The total length of the water level meter should correspond with the length of the <br /> measuring tape_ In addition, the individual marks oa the cable should con=pond with the <br /> comet footage. If the cable does not match the measuring tape then the differenceCif consistent) <br /> should be calculated. as a percentage, (Lel., 100 foot cable measures 102 feet 98°!0). All <br /> measurements with the'cable should-then be .multiplied by 0.98 to correct for the error. If the <br /> individual footage marcs are not placed correctly and arc not consistent in their deviation, the <br /> instrument should be replaced. <br /> If the water level indicator is constructed of a cable then calibration will be performed once per <br /> year. If there is a discrepancy, the conversion factor will be marked directly on the instrument. <br /> Water level indicators constructed of tape are more subject to stretching and should be calibrated <br /> every 6 months and marked with the appropriate conversion.. <br /> Calibradon data for each instrument will.be.recorded.and.kepUa a.binder at the:office forfuwre_ - <br /> reference. The most recent calibration results will also be recorded in the technicians field notes. <br /> There is no specific form for water level indicator calibration. <br /> 2H Meter <br /> pH is subject to significant variations due to temperature, buffering capacity of the water, and <br /> instrinnent drift For this reason pH meters must be-calibrated.before and after sampling on each.. <br /> day and at least once more during the day. To calibrate a pH meter,the instrument 'reading is - <br /> adjusted to read corrccdy for solutions with a standard pK <br /> Standard solutions arc mixed fresh, according to package instrcQ ,-for each satnpling'event. <br /> Standard solutions or powders for pH 4,7, and 10 are commercially available. These standards <br /> -are purchased fresh and-discarded after sheff life has expired. Shelf livesvary depending on the <br /> brand of standards used. If pre-prepared solution is used,the expiration daze of the solution will <br /> be noted on the calibration log. <br /> Although different brands of pH meters vary, raltbration procedturs are similar for an of them. <br /> A geaerali calibration procedure follows: <br /> 1. Turn on the instrument,check the battery,and allow to wartit up if necessary.. -- <br /> 23.493$49•FOIt23IOR325 A•Z J*14,2404 <br /> COPYrf t ZWO KkW Wa.baa. <br />