increasing trend for field pH at AMW-5R is not observed when the data are limited to the period <br /> of April 1999 to February 2012, indicating that values have stabilized in the past thirteen years. <br /> The first quarter 2012 field pH value at AMW-11 (7.34 s.u.) is within the range of values <br /> observed at that well since March 1994 (6.60 to 8.40 s.u.), and is within the National Secondary <br /> Drinking Water Standard range of 6.5 to 8.5 s.u. The increasing trend for field pH at AMW-11 is <br /> not observed when the data are limited to the period of May 2003 to February 2012, indicating <br /> that values have stabilized in the past nine years. The first quarter 2012 field pH value at AMW- <br /> 19BR(7.40 s.u.) is within the range of values observed at that well since November 2007 (6.74 to <br /> 7.90 s.u.), and is within the National Secondary Drinking Water Standard range of 6.5 to 8.5 s.u. <br /> The increasing trend for field pH at AMW-19BR is not observed when the data are limited to the <br /> period of November 2008 to February 2012, indicating that values have stabilized in the past four <br /> years. <br /> The first quarter 2012 field pH value at AMW-1 (6.49 s.u.) is within the range of values observed <br /> at that well since June 1994 (6.24 to 7.60 s.u.), but is below the National Secondary Drinking <br /> Water Standard range of 6.5 to 8.5 s.u. However,the decreasing trend for field pH at AMW-1 is <br /> not observed when the data are limited to the period of September 1996 to February 2012, <br /> indicating that values have stabilized in the past sixteen years. <br /> The first quarter 2012 field specific conductance value at AMW-1 (1,396 umhos/cm) is within the <br /> range of values observed at that well since June 1994 (492 to 2,180 umhos/cm). The increasing <br /> trend for field specific conductance at AMW-1 is not observed when the data are limited to the <br /> period of April 1998 to February 2012, indicating that values have stabilized in the past fourteen <br /> years. The first quarter 2012 field specific conductance value at AMW-5R (1,267 umhos/cm) is <br /> within the range of values observed at that well since March 1994(280 to 1,490 umhos/cm). The <br /> increasing trend for field specific conductance at AMW-5R is not observed when the data are <br /> limited to the period of July 2001 to February 2012, indicating that values have stabilized in the <br /> past eleven years. <br /> The first quarter 2012 concentration of sulfate at AMW-5R (67 mg/L) is within the range of <br /> concentrations observed at that well since March 1994 (<1 to 105 mg/L), and is below the <br /> National Secondary Drinking Water Standard of 250 mg/L. The increasing trend for sulfate at <br /> AMW-5R is not observed when the data are limited to the period of October 1998 to February <br /> 2012, indicating that concentrations have stabilized in the past fourteen years. The first quarter <br /> 2012 concentration of sulfate at AMW-10 (47 mg/L) is within the range of concentrations <br /> observed at that well since March 1994 (18 to 80 mg/L), and is below the National Secondary <br /> Drinking Water Standard of 250 mg/L. The increasing trend for sulfate at AMW-10 is not <br /> observed when the data are limited to the period of May 2001 to February 2012, indicating that <br /> concentrations have stabilized in the past eleven years. <br /> The first quarter 2012 concentration of TDS at AMW-5R (840 mg/L) is within the range of <br /> concentrations observed at that well since March 1994 (213 to 880 mg/L), but is above the <br /> National Secondary Drinking Water Standard of 500 mg/L. However, the increasing trend for <br /> TDS at AMW-5R is not observed when the data are limited to the period of May 2001 to <br /> February 2012, indicating that concentrations for this constituent have stabilized in the past <br /> eleven years. <br /> The first quarter 2012 field turbidity value at AMW-5R (>1000 NTUs) is consistent with the <br /> range of values observed at that well since May 1995 (<0.01 to >1000 NTUs). The increasing <br /> trend for field turbidity at AMW-5R is not observed when the data are limited to the period of <br /> November 2005 to February 2012, indicating that values have stabilized in the past seven years. <br /> 7 <br />