Laserfiche WebLink
CONDITIONS FOR P-2730-1-0 Page: 2 <br /> 7. If this unit remains in a Participating District for more than 24 hours, the operator shall notify that <br /> District within 2 calendar days of the nature and estimated duration of operations, and the name and <br /> phone number of a contact person. _ <br /> 8. Except for emergency operations, this unit shall not be operated within 1,000 feet of any K-12 school, <br /> unless the public and student notification requirements of the CH&SC Section 42301.6 have been <br /> satisfied. <br /> 9. No air contaminant shall be released into the atmosphere which causes a public nuisance. <br /> 10. No air contaminant shall be discharged into the atmosphere for a period or periods aggregating more <br /> than 3 minutes in any one hour which is as dark or darker than Rmglemann 1 or equivalent to 20% <br /> opacity. <br /> 11. Particulate matter emission concentration shall not exceed 0.10 grains per standard dry cubic foot. <br />