Laserfiche WebLink
CALTECH Environmental Laboratories <br /> O68l:t Rc,ecra,s A%enuc Fluar ic-in' L . 9o723-3 146 <br /> �c,i��rf�L?ile 1 5Ci� a, 1562' 272-2-/Y(, <br /> QA/QC Report <br />' Method 8260B <br /> IMatrix Water <br /> Date Analyzed 9124102 <br />' Units ug/L <br />' Perimeters LSC LCSD Spike LCS % LCSD Na Limits RPD <br /> _ Added Rec. Rec. <br /> i 1,1-Dichloroethene 46 45 50 92 90 70-130 2 <br />' Benzene 43 43 50 83 86 70-130 4 <br /> Trichloroethene 49 56 50 98 112 70-130 14 <br /> ,'Toluene 52 54 50 104 108 70-130 4 <br />' iChlorobenzene 53 59 50 106 118 70-130 11 <br /> i m, -X lenes 102 104 100 102 1 104 70-130 2 <br /> • <br /> 1 <br /> LCS Laboratory Control Standard <br />' LCSD Laboratory Control Standard Duplicate <br /> RPD Relative Percent Difference of LCS and LCSD <br /> 1 <br /> PerimetersBlank Limas RPD <br /> �1,1-Dichloroethene 0 70-130 <br /> Benzene 0 70-130 <br />' Trichloroethene 0 70-130 <br /> Toluene 0 70-130 <br /> Chlorobenzene 0 70-130 <br />' ,m,p-X lenes 0 70-130 <br /> I <br />' TOTAIA N' DEDIC ATE D 10 CUSTOMER SATISFACTION <br />