Laserfiche WebLink
Electronic Leak Detector Test Data Sheet <br /> Site Name Lodi CA FO Term(Intl) Date 03/05/20 <br /> Address 2500 West Turner Road <br /> Lodi CA 95242 <br /> Test Information <br /> 1 ? 3 4 <br /> Product Diesel <br /> Manufacturer Incon <br /> Model TS-LSU 500 <br /> Full Operating Pressure (PSI) 26 psi <br /> F/E Holding Pressure (PSI) 22 psi <br /> Did Alarm sound with 3GPH test. YES <br /> How many turbine cycles before alarm. 2 cycles <br /> Is turbine shut down when in alarm. NO <br /> Test Leak Rate (ml/min)(gph) 189 ml. <br /> PASS or FAIL PASS <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced <br /> facility according to the equipment manufacturers procedures and limitations and the results <br /> as listed are to my knowledge true and correct. The mechanical leak detector test pass/fail <br /> is determined using a low flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor sunwest engineering inc. <br /> Technician Ruben Becerra Lic# 1655 <br /> �Ruben Becerra Digitally signed by Ruben Becerra <br /> Signature Date: 2020.03.05 10:22:53 -08'00' <br />