Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: Tank Manufacturer X Industry Standard 1 Professional Engineer <br /> Other(Specify) <br /> Test Method Used: Pressure X Vacuum Hydrostatic <br /> Other(Specify) <br /> Test Equipment Used: Gast Vacuum PumpNacuum Gauges in Hg. Equipment Resolution: - V'x-30"Hg. <br /> Tank# I <br /> Tank#2 Tank# Tank <br /> Is Tank Exempt From Testing?' No No <br /> Tank Capacity: 6K 6K <br /> Tank Material: Jacketed DW Steel Jacketed DW Steel <br /> Tank Manufacturer: Trusco Trusty <br /> Product Stored: Diesel Regular 87 <br /> Wait time between applying 5 Minutes 5 Minutes <br /> vacuum and startin test: <br /> Test Start Time: 12:50 12:55 <br /> Initial Reading(Ri): -6"Hg. -6"Hg. <br /> Test End Time: 1:50 1:55 <br /> Final Reading(Rr): -6"Hg. -6"Hg. <br /> Test Duration: I Hour I Hour <br /> Change in Reading(RF-Ri): 0"Hg. 0"Hg. <br /> Pass/Fail Threshold or Criteria: No Loss in Hg. No Loss in Hg. <br /> Teat Result: Pass Pass <br /> Was sensor removed for testing? Yes Yes <br /> Was sensor properly replaced and <br /> verified functional after teson Yes Yes <br /> _Comments—(include information on repairs made prior to testing and recommended oll w- p for failed t t) <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />