Laserfiche WebLink
A J OA U I Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> TULARE FARMS LLLP 2771 E FRENCH CAMP RD, MANTECA January 10, 2020 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> OBSERVATION: The designated operator failed to check and note all required items on the visual inspection <br /> reports. The incorrect and missing information included the following from all the inspection reports: <br /> -The DO failed to add a description to all the components marked N/A from section VII through XI <br /> REGULATION GUIDANCE: During the visual inspection, the designated operator shall check that all required <br /> testing and maintenance for the UST system have been completed and shall check all required items on the report. <br /> CORRECTIVE ACTION: Ensure that designated operators performing visual inspections at this facility are including <br /> all of the required information on the reports. <br /> This is a minor violation. <br /> 301 HSC 25292.1(a) UST system is not operated to prevent unauthorized release, including spills and overfills. <br /> OBSERVATION: The fuel filters under the dispensers are not located to allow drips and leaks to drain back into the <br /> UDC. <br /> REGULATION GUIDANCE: The underground storage tank system shall be operated to prevent unauthorized <br /> releases. <br /> CORRECTIVE ACTION: Immediately provide approved secondary containment for the filters under permit and <br /> inspection by the EHD. <br /> This is a Class II violation. <br /> 307 CCR 2631(g), 2632(c) Monitoring system of the interstitial space of a double walled system not maintained. <br /> OBSERVATION: The diesel annular sensor got stuck and not tested, therefore, the tank is not monitored. <br /> REGULATION GUIDANCE: The interstitial space shall be monitored with a monitoring system connected to an <br /> audible and visual alarm system. <br /> CORRECTIVE ACTION: Immediately contact a properly licensed, trained, and certified contractor to replace the <br /> failed component with a functional component(LG 113-x listed, if applicable), and obtain a permit within one <br /> business day from the EHD, if needed. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by February 9, 2020. <br /> Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate ($152). To schedule an <br /> appointment, please call (209) 468-3420. <br /> FA0003508 PR0234251 SCO01 01/10/2020 <br /> EHD 23-01 Rev.9/20/2019 Page 5 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />