Laserfiche WebLink
Lancaster• Re ort <br /> Laboratories Analysis ►� <br /> 7 <br /> 2425 New Holland Pike,PO lam 12425 Lancaster,PA 17605-242 5•717-65&2300 Fax 717-656.2681•www Iar1C88terlabs com <br /> Page 4 of 4 <br /> Quality Control Summary <br /> Client Name ChevronTexaco Group Number 848479 <br /> Reported 04/25/03 at 05 28 PM <br /> Surrogate Quality Control <br /> Limits 81-120 82-112 - - -- — -- 85-112- ---_ _-- -_ 83-113_ <br /> Analysis Name BTEX + Oxygenates by 8260B <br /> Batch number P031111AA _ 4-Bromofluorobenzene <br /> Dibromofluoromethane 1,2-Dichloioethane-d4 Toluene-d8 <br /> 4027638 102 105 96 94 <br /> 4027639 101 100 102 100 <br /> 4027640 101 103 102 98 <br /> 4027641 101 103 103 98 <br /> Blank 102 104 101 100 <br /> LCS 300 100 89 90 <br /> MS 101 104 101 103 <br /> MSD 101 102 101 103 <br /> Limits 81-120 82-112 85-112 83-113 <br /> Analysis Name BTEX + Oxygenates by 6260B <br /> Batch number P031112AA 4-Bromofluorobenzene <br /> Dibromofluoromethane 1,2-Dichloroethane-d4 Toluene-de <br /> 4027642 105 103 303 100 <br /> Blank 104 103 103 99 <br /> LCS 104 101 91 91 <br /> MS 103 103 101 102 <br /> MSD 105 104 101 102 <br /> Limits 81-120 82-112 _ _ 85-_112 _ _ _ _ _ _ 83-113 - <br /> *-Outside of specification <br /> (1) The result for one or both determinations was less than five times the LOQ • <br /> (2) The background result was more than four times the spike added <br />