Laserfiche WebLink
PEI/RP1200-12 <br /> pipe, it is not considered to be liquid-tight.This and secondary containment. 'I'he vacuum level is <br /> visually indicates a test failure. monitored Fora I-minute period. <br /> 6.3.5 Test Procedure. 6.4.3 Test Equipment. Test equipment shall <br /> 1.Slowly apply Y 1 a vacuum of 30 inches water include: <br /> column to the spill bucket and close the valve. vacuum test apparatus (The test apparatus may <br /> If a 30-inch water column vacuum cannot he be available From the spill-bucket manufacturer. <br /> attained, the spill bucket fails the test. See it includes an air pressure regulator, a vacuum <br /> Appendix 13 for pressure and vacuum conver- source, a vacuum gauge with a minimum 0-30 <br /> cions. inch water colwnn range, a test fitting and a <br /> 2.Start the time-measurement device and record control valve.'1'he control valve is used to adjust <br /> the initial vacuum level shown on the gauge. the vacuum level.); <br /> 3.After I minute, record the ending vacuum level. stopwatch or other time-measurement device <br /> capable of measuring a I-second increment. <br /> Upon completion of the test, release the. vacuum, <br /> remove the test apparatus and the gasketing mate- WARNING: Use only an air-operated vacu- <br /> rial from the spill bucket and replace the original um source or a vacuum pump powered by <br /> COW'. an explosion-proof motor. Vacuum pumps <br /> with electric motors that are not explo- <br /> sion-proof may ignite flammable vapors. <br /> If a portable air compressor Is used, it <br /> 1 r should be located at least 20 feet away <br /> I <br /> x from the venturi-eductor or outside any <br /> Class I, Division 1 area. <br /> ✓ic Vacuum <br /> Source Control Valy <br /> r <br /> 0-30'Water Column <br /> Vacuum Gauge <br /> Regulator <br /> FIGURE 6.3. The vacuum test method can detect a spill <br /> bucket leak by measuring the change in vacuum level <br /> during the test. <br /> 6.3.6 Pass/Fail Criteria. If the.ending vacuum <br /> level is 26 inches water column or greater, the spill <br /> bucket passes the test. <br /> If file ending vacuum level is less than 26 inches <br /> water column,the spill bucket fails the test. <br /> 6.4 Double-Walled Spill Bucket Integrity Testing— FIGURE 6-4. Check lines and connections to ensure <br /> Vacuum Test Method. that they are leak-tight before starting the test. <br /> 6.4.1 Purpose. 'T'his method is used to test the <br /> integrity of the primary and secondary containment 6.4.4 Preparation. <br /> of the double-walled spill hucket. <br /> 1. Remove and properly dispose of any liquid and <br /> 6.4.2 Description of Test. A partial vacuum is debris (leaves, sediment and trash) in the spill <br /> applied to the interstitial space between the primary bucket. <br /> pei.org <br />