Laserfiche WebLink
S0 JOA U 1 Environmental Health Department <br /> U ;� i Y I <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> WILSON WAY CHEVRON 437 N WILSON WAY, STOCKTON February 04, 2020 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 306 CCR 2630(d), 2641(a) Monitoring equipment is not installed or maintained to detect a leak at the earliest <br /> opportunity. <br /> OBSERVATION: The 208 sensor in UDC5/6 was observed to be on the its side and not located to detect a leak at <br /> the earliest opportunity. <br /> REGULATION GUIDANCE: Monitoring equipment shall be maintained to be able to detect a leak at the earliest <br /> possible opportunity. <br /> CORRECTIVE ACTION: The sensor was relocated to the lowest point of the sump by the service technician. <br /> Ensure that all monitoring equipment is maintained and located to detect a leak at the earliest opportunity. <br /> This was corrected on site. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> The monitoring system certification was conducted today and was not witnessed by EHD. Looked inside all <br /> sumps and UDCs. Verified sensor locations and piping communication. Verified spill bucket 5 gallon capacity. <br /> Paperwork inspection is still needed. A checklist was provided at the time of inspection. A complete report will <br /> be provided at the time of paperwork inspection. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, within 30 days of receiving the complete inspection report. <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: February 04, 2020 Inspector: Inspector Phone: <br /> Printed Name and Title: SHEWIT WOLDEAREGAY, EH Specialist (209)468-0216 <br /> aman mehroke, manager <br /> FA0002313 PR0506406 SCO01 02/04/2020 <br /> EHD 23-01 Rev.9/20/2019 Page 4 of 4 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />