Laserfiche WebLink
Recommended Practices for the Testing and Verification of Spill, Overfill, Leak Detection and Secondary Containment Equipment at UST Facilities <br /> sibility of accidentally imposing a high vacuum <br /> that could damage the tank. The use of the valve , <br /> is recommended because it limits the vacuum <br /> that can be applied to the interstitial space .) ; Tank Vacuum, Capaclty, Duration, <br /> Type Inches Hg gallons hours <br /> ® vacuum gauge with a range of 0 inches to 30 < 20,000 1 <br /> inches Hg graduated in increments of 0.5 inches Fiberglass 10 <br /> Hg or less ; 2o,oao+ 2 <br /> < 20,040 1 <br /> ® toggle valve and vacuum hose; steel 6 <br /> 20,000+ 2 <br /> 4d stopwatch or other time-measurement device <br /> capable of measuring a l -second increment; <br /> is plumber' s plug. 4.2.9 Pass/Fall Criteria. If there is no loss in <br /> vacuum level, no liquids are drawn into the inter- <br /> 4. 2 .9 Test Procedure. stitial space during the test duration shown in Table <br /> 4. 1 , and the tank secondary containment area has <br /> 1.. Install the plumber 's plug in the interstitial no additional fluid than at the start of the test, then <br /> nser(s) below any tees. the tank secondary containment passes the test. <br /> 2. Connect the vacuum gauge, valve and the If there is any vacuum lost during the test or liquids <br /> vacuum-generating device to the fitting on the are drawn into the interstitial space, then the tank <br /> plumber' s plug. The valve should be between secondary containment fails the test. <br /> the vacuum source inlet and the pressure <br /> gauge. The gauge should be between the valve 4.3 Tank Secondary Containment Integrity Testing <br /> and the fitting so it will read the interstitial vac- ® Liquid-Filled Test Methods <br /> uum when the valve is closed. The automatic <br /> vacuum shutoff valve is located at the inlet of 4.3.1 General. This test method tests the integ- <br /> the vacuum-producing device and should be rity of the liquid-filled interstitial space. There are a <br /> set at a minimum of 10 percent and no more number of variables that affect this test, such as inter" <br /> than 2 inches Hg above the test vacuum. stitial space volume, temperature, water table and <br /> product level in the primary tank. Refer to Appendix <br /> 3 . Ensure all connections are airtight. A for specific manufacturers' test procedures. <br /> 4. Start the vacuum-generating device, and open 43 .2 Purpose. This general method is used to <br /> the valve. <br /> test the integrity of the liquid-filied secondary con- <br /> t. Pull the vacuum to 10 inches Hg for fiberglass tairi mnt of a UST. <br /> tanks and 6 inches Hg for steel tanks . Close the <br /> valve. 4.3.3 Description of Test. Liquid is added to <br /> the interstitial space of the tank and the level is <br /> 6 . Allow the vacuum to stabilize for a minimum brought up into the interstitial riser. The liquid level <br /> of 5 minutes at the specified vacuum level. If is monitored for a specified period of time. If the <br /> a stable vacuum cannot be maintained, test liquid level is maintained, then the containment <br /> equipment shall be inspected for leakage. system has passed the test. <br /> Repeat steps 4 and 5 until a stable vacuum is <br /> achieved. If a stable vacuum cannot be main- 4,3.4 Test Conditions. The primary contain- <br /> tained, the tank secondary containment integ- ment may contain any level of product. Determine <br /> rity test fails. whether the groundwater depth is above the bottom <br /> 7. When the vacuum level stabilizes, record the of the tank. Consult specific manufacturer's proce- <br /> vacuum level and the test start time. dures in regards to groundwater and performing the <br /> test. No bulk deliveries shall occur within 8 hours <br /> S . Observe the vacuum level for the period of .prior to conducting or during the test. No dispens- <br /> time shown in Table 4- 1 . 1Ing <br /> may occur during the duration of the test. <br /> 9. Record the final time and vacuum level. 4,3. 5 Preparation. Determine the volume of <br /> 10. Check the interstitial space for accumulation of the tank and identify the test being performed . <br /> liquids . Tank volume information is available from facility <br /> peLorg 0 <br />