Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ® Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum N Hydrostatic <br /> Test Equipment Used: <br /> Sump/UDC ID UDC 1/2 UDC 314 UDC 5/6 UDC 7/8 <br /> Sump Manufacturer Bravo Bravo Bravo Bravo <br /> Sump Depth (inches) 32 32 32 32 <br /> Sump Bottom to Top of 12 12 12 12 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:27am 9:56am 11:09am 9:45am <br /> Initial Reading 0.8432 0.5169 0.4773 1.8549 <br /> Test End Time 9:42am 10:1 lam 11:24am 10:OOam <br /> Final Reading 0.8444 0.5163 0.4772 1.8559 <br /> Change in Reading 0.00118 0.00062 0.00018 0.00100 <br /> Pass/Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results ® Pass ❑ Fail M Pass ❑ Fail N Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID UDC 9110 UDC 11/12 <br /> Sump Manufacturer Bravo Bravo <br /> Sump Depth (inches) 32 32 <br /> Sump Bottom to Top of 12 12 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 11:10am 11:28am <br /> Initial Reading 1.0425 4.1185 <br /> Test End Time 11:25am 11:43am <br /> Final Reading 1.0433 4.1175 <br /> Change in Reading 0.00083 0.00100 <br /> Pass/Fail Criteria 0.002 0.002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />