OPW Installation , Operation and Maintenance Manual , Page 27 Executive Order VR-401P,,,
<br /> OPW Installation and Maintenance Instructions
<br /> 1711T- 7085 - EVR Vapor Recovery Cap Instructions
<br /> IMPORTANT : Please read these warnings and use proper warranty claim documentation required.)
<br /> the assembly instructions completely and carefully This warranty shall not apply to any product that has
<br /> before starting . Failure to do so may cause product been altered in any way, which has been repaired by
<br /> failure , or result in environmental contamination due any party other than a service representative
<br /> to liquid leakage into the soil , creating hazardous authorized by OPW, or when failure is due to
<br /> spill conditions . misuse, or improper installation or maintenance .
<br /> OPW shall have no liability whatsoever for special,
<br /> IMPORTANT : Check to make sure the unit is intact incidental or consequential damages to any party,
<br /> and undamaged and all parts have been supplied . and shall have no liability for the cost of labor,
<br /> Never substitute parts for those supplied . Doing so freight, excavation, cleanup, downtime, removal,
<br /> may cause product failure . reinstallation, loss of profit, or any other cost or
<br /> charges.
<br /> WARNING -DANGER : Using electrically operated For any product certified to California 2001
<br /> equipment near gasoline or gasoline vapors may standards, OPW warrants that products sold by it
<br /> result in a fire or explosion , causing personal injury are free from defects in material and workmanship
<br /> and property damage . Be sure that the working area for a period of one year from date of manufacture or
<br /> is free from such hazards , and always use proper one year from date of registration of installation not
<br /> precautions . to exceed 15 months from date of manufacture by
<br /> NOTE : At all times when product is in the storage OPW.
<br /> tank keep the riser pipe capped , so the vapors THIS WARRANTY IS IN LIEU OF ALL OTHER
<br /> cannot escape into the environment . WARRANTIES , EXPRESS OR IMPLIED , AND
<br /> Notice : OPW products must be used in compliance SPECIFICALLY THE WARRANTIES OF
<br /> with applicable federal , state , and local laws and MERCHANTABILITY AND FITNESS FOR A
<br /> regulations . Product selection should be based on PARTICULAR PURPOSE , THERE ARE NO
<br /> physical specifications and limitations and WARRANTIES WHICH EXTEND BEYOND THE
<br /> compatibility with the environment and material to be DESCRIPTION ON THE FACE HEREOF .
<br /> handled . All illustrations and specifications in this Preventative Maintenance :
<br /> literature are based on the latest production Annually inspect the cap and gasket for cracks or
<br /> information available at the time of publication . deformation . Replace if necessary .
<br /> Prices , materials , and specification are subject to
<br /> change at any time , and models may be Replacement Parts :
<br /> discontinued at any time , in either case , without Nitrile Gasket , P/N : H10886M
<br /> notice or obligation .
<br /> 1711T Vapor Recovery Cap Function Testing
<br /> Standard Product Warranty
<br /> OPW warrants that products sold by it are free Clamping Test
<br /> from defects in materials and workmanship for a Clamping force is to be between 25 and 45 lbs .
<br /> period of one year from the date of manufacture by
<br /> OPW (ECO products two years from date of Pressure Leak Testing
<br /> manufacture .) Proof of purchase may be required. Cap should hold 3 . 5 PSI for 30 seconds . If the cap
<br /> As the exclusive remedy under this limited warranty, does not hold this pressure , replace the gasket and
<br /> OPW will, at its sole discretion, repair, replace, or re-test .
<br /> issue credit for future orders for any product that
<br /> may prove defective within the one -year date of Lock Test
<br /> manufacture period (repairs, replacements, or Clamp cap onto adaptor and insert 5/ 16 " diameter
<br /> credits may be subject to prorated warranty for pin into lock hasp . Cap should not disengage from
<br /> remainder of the original warranty period, complete adaptor .
<br /> O 9393 Princeton-Glendale Road , Cincinnati , Ohio 45011
<br /> 1 -800422-2525 Domestically , 513-870-3315 Internationally, www, opw-fc .com
<br /> RMfn COP' FAv. Copyright , 2009 OPW Fueling Components Inc . , Cincinnati , OH
<br /> printed in U . S .A . p/n 204011 — 07/09