Laserfiche WebLink
A�Lffoirda—Te,' t 4162 nd Street <br /> Galt, CA 95632 <br /> (209) 744-0113 Fax (209) 744-0116 <br /> E.O.VR-204 <br /> Veeder-Root In-Station Diagnostics Balance Vapor Flow Meter Operability Test Procedure <br /> Permit Number: N-9259 Date of Test: 11-12-19 Time: 1030 <br /> Site Name: ARCO STOCKTON <br /> Site Address: 6009 N EL DORADO ST. <br /> City: STOCKTON, CA Zip: 95207 Technician: FELIX RAMIREZ <br /> VST: 3001003870 <br /> District: SJVAP NORTH Veeder-Root: B34976 <br /> Calibration Date: 10-17-2019 <br /> Flow ISD Flow Meter Gas Flow Meter <br /> Fueling o Pass <br /> /o / <br /> Meter Point Start Stop Diff.(in gal) Start Stop Diff.(in ef) Converted Diff. Fail <br /> Serial No. Diff.(in al) <br /> 74688 1-2 62116.127 62123.440 7.313 8910 9010 1 7.481 -2.2 Pass <br /> 74612 3-4 16840.887 16848.506 7.619 9010 9110 1 7.481 1.8 Pass <br /> 74687 5-6 49886.105 49893.636 7.531 9110 9210 1 7.481 0.6 Pass <br /> 75796 7-8 73153.762 73161.576 7.814 9210 9210 1 7.481 -4.4 Pass <br /> 74607 9-10 49311.487 49318.920 7.433 9210 9310 1 7.481 -0.6 Pass <br /> 73046 11-12 85403.916 85410.916 7.429 9310 9410 1 7.481 -0.5 Pass <br /> o ISD_Differencegarrons —Gas_Flow_Meter_Differencegarro <br /> Gallons = Cubic—Feet x 7.481 /oDifference= x 100 <br /> Gas_Flow_Meter_Differenceg,,110. <br /> I declare, under penalty of perjury under the laws of the state of California that based on information and belief formed after reasonable inquiry, the <br /> statements and information provided in this document are true, accurate, and complete. <br /> Signature of Technician: 1� Date: 11-12-19 <br /> Ver. 1.0—09.18.08 <br />