Laserfiche WebLink
DocuSign Envelope ID: 8CE92D2A-3F50-43AD-8C8D- 1E49DDAB6D53 <br /> May 19 , 2020 <br /> Shewit Woldearegay <br /> Environmental Health Department <br /> San Joaquin County <br /> 1868 East Hazelton Avenue <br /> Stockton , CA 95205 <br /> RE : Costco Gasoline — NOV Response <br /> 2440 Daniels Street, Manteca , California 95337 <br /> Costco Loc. No. 1031 / Barghausen Job No. 12919 . 5 <br /> Dear Ms. Woldearegay , <br /> This letter is in response to your May 7 , 2020 inspection at the Costco gas station located at 2440 Daniels <br /> St, Manteca . <br /> Our Manteca gas station opened in 2008 , so it is continuously monitored via a VPH system per SB2481 <br /> requirements. Additionally, all Costco gas station alarms generate an immediate service response by <br /> Gilbarco Veeder-Root's Insite 360 monitoring service , including all liquid and VPH sensors in the <br /> system . All sensors are tested at least annually for operability and for correct placement in the tank and <br /> dispenser sumps. <br /> Specifically , Costco takes issue with the following violation : <br /> 316 HSC 25290 . 1 (c3) , 25290 . 2 (c3) Secondary containment not constructed to prevent water <br /> intrusion (after Jul 2003) . <br /> OBSERVATION : Approximately 3 cups of liquid was found in the additive fill sump . <br /> REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any <br /> water intrusion into the system by precipitation , infiltration , or surface runoff. <br /> CORRECTIVE ACTION : The service technician removed all of liquid from the additive <br /> fill sump and returned the sensor to its proper location . <br /> This was corrected on site. <br /> This is a repeat violation . Class ll . <br />