6. Verify that the water level will not cover electrical threaded connections before water <br /> testing. If the water will exceed threaded connections to the dispenser conduit seal off one <br /> must ensure no water will enter through that point. This assumes that the conduit threaded <br /> connections are not liquid tight. Visual testing only allowed on initial installation to pass <br /> NO drips leaks are allowed. If outside of sump can not be observed a minimum 5 hour test <br /> must be observe with a level drop no greater than 1/8". Alternative testing can be used such <br /> as electronic level probe, which can use its accuracy to reduce test time. <br /> 7. E.g Data collection time Typical 12"x 32"Box and fail rate of.05 GPH <br /> Failure,if rate exceeds Resolution/accuracy Data Time <br /> 0.0030 in 6 minutes Better than .0005" 6 minutes <br /> 0.0070 in 15 minutes .001 to .002" 15 minutes <br /> 0.0150 in 30 minutes .002 to .003" 30 minutes <br /> 8. After the completion of the water test, certify if the test has passed based on the schedule <br /> above. If you experience problems contact Bravo for assistance(323)888-4133. <br /> 9. Remove water and properly dispose of and manually dry float cup area. Next, remove <br /> weight off the float, if applicable, and make sure the chain is properly adjusted as indicated <br /> on installation maintenance instructions. This includes verification of float trip function and <br /> proper lead seal crimping to prevent future tampering. To adjust chain,refer to Bravo <br /> Installation Instructions page 7 of B2000 Shallow Box and page 6 of the B-8000 Deep Box. <br /> 10. NOTE: If Local Jurisdictions have high requirements than these please use their test <br /> protocols. <br /> Thank You, <br /> Don Mukai P.E. <br /> Bravo Engineering <br /> f:\engineering\winword0ocumentOut\Doc01-06.doc <br />