Laserfiche WebLink
f11ra-o d 1 e t 416 2"d Street <br /> Galt, CA 95632 <br /> (209) 744-0113 Fax (209) 744-0116 <br /> E.O.VR-204 <br /> Veeder-Root In-Station Diagnostics Balance Vapor Flow Meter Operability Test Procedure <br /> Permit Number:N-2522 Date of Test: 9/19/2018 Time: <br /> Site Name: WEST LANE CHEVRON <br /> Site Address: 4747 WEST LANE <br /> City: STOCKTON, CA Zip: 95210 Technician: ZANE NIMMO <br /> VST: 3000839502 <br /> District: SJVAPCD Veeder-Root: A28446 <br /> Calibration Date: 3/10/2018 <br /> Flow ISD Flow Meter Gas Flow Meter <br /> Meter Fueling Converted %Diff. Pass/ <br /> Serial r Point Start Stop Diff.(in gal) Start Stop Diff.(in ef) Diff, in al Fail <br /> 2 4 9 6 5 1 /2 26.688 33.881 7.193 6.885 0.920 4.47 Pass <br /> 2 4 9 5 8 3/4 85.566 92.512 6.946 6.607 0.920 5.13 Pass <br /> 2 9 2 6 5 5/6 54.623 61.108 6.485 6.440 0.861 0.69 Pass <br /> 2 5 0 3 1 7/8 16.351 21.312 4.961 5.508 0.736 -9.93 Pass <br /> N/A 9/ 10 <br /> N/A 11 / 12 <br /> o ISD_Differencegallons -Gas_Flow_Meter_D erencegglr°, <br /> Gallons= Cubic Feet x 7.481 /oDifference= X100 <br /> Gas_Flow_Meter_Di <br /> erencegQuo„s <br /> I declare, under penalty ofperjury under the laws of the state of California that based on information and belief formed after reasonable inquiry, the <br /> statements and information provided in this document are true, accurate, and complete. <br /> Signature of Technician: Date: 9/19/2018 <br /> Ver. 1.0—09,19.09 <br />