Laserfiche WebLink
bp Hi VIED <br /> JUL 13 2018 <br /> ENVIRONMENTAL <br /> Line Leak Detector Test Data Sheet HEALTH LEP/`RTMENT <br /> Station # Arco 7149 Date 6/20/2018 20 <br /> Address 9484 West Lane Stockton, CA 95210 <br /> Test Information <br /> 1 2 3 4 5 <br /> Product 87 91 DSL <br /> Manufacturer FE VP RJ <br /> Model MLD LD2O0O FXVI <br /> Full Operating Pressure(psi) 28 34 30 <br /> Line Bleed Back(ml) 150 180 150 <br /> Trip Time (sec) 6 2 7 <br /> Metering Pressure(psi) 10 18 10 <br /> F/E Holding Pressure (psi) 28 30 28 <br /> Test Leak Rate(ml/min)(gph) 189 ml 189 ml 189 <br /> PASS or FAIL pass pass pass <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Gettler Ryan Inc <br /> Technician Da id RoU Lic#220793 <br /> Signature <br />