Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: a Tank Manufacturer L Industry Standard a Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum ❑Hydrostatic <br /> Other(Spec) <br /> Test Equipment Used: Equipment Resolution: <br /> Tank# 1 Tank#2 Tank#3 Tank# <br /> Is Tank Exempt From Testing? Yes Yes Yes <br /> Tank Capacity: 15K 12K 12K <br /> Tank Material: Fiberglass Fiberglass Fiberglass <br /> Tank Manufacturer: Containment Containment Containment <br /> Solutions/OC Tank Solutions/OC Tank Solutions/OC Tank <br /> Product Stored: Regular 87 Super 91 Diesel <br /> Wait time between applying *Exempt *Exempt *Exempt <br /> vacuum and starting test: See comments See comments See comments <br /> Test Start Time: <br /> Initial Reading(RI): <br /> Test End Time: - <br /> Final Reading(RF): <br /> Test Duration: JUL 17 207 <br /> Change in Reading(RF-Rj): <br /> Pass/Fail Threshold or Criteria: NVIRIO'�t <br /> ENI <br /> Test Result: <br /> FBF <br /> Was sensor removed for testing? <br /> Was sensor properly replaced and <br /> verified functional after testin ? <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> *Tanks have Brine filled Annulars,and are Exempt from periodic Testing. <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23, Section 2637(a)(6)} <br />