Laserfiche WebLink
ffo rd a- 1 e t 4162 nd Street <br /> Galt, CA 95632 <br /> (209) 744-0113 Fax (209) 744-0116 <br /> E.O.VR-204 <br /> Veeder-Root In-Station Diagnostics Balance Vapor Flow Meter Operability Test Procedure <br /> Permit Number:N-292 Date: 9-17-18 <br /> SITE NAME: SHORT STOP <br /> Site Address:20 WEST TURNER LANE <br /> City:LODI CA, Zip: 95240 Technician: DAVE WINKLER <br /> VST: 30001531961 <br /> District: SJV Veeder-Root: B34975 <br /> ISD Flow Meter Gas Flow Meter <br /> Flow Fueling ° Pass/ <br /> Meter Point Start Stop Diff. (in d /°al) Start Stop Diff.(in ef) Converted Diff. Fail <br /> Serial No. Diff.(in gal) <br /> 71404 1 208722.669 20830.314 7.645 6700 6800 1.00 7.481 2.1 Pass <br /> 71431 2 113558.666 113566.221 7.555 6800 6900 1.00 7.481 .9 Pass <br /> 72323 3 151872.064 151879.124 7.060 6900 7000 1.00 7.481 5.6 Pass <br /> 72321 4 90095.503 90103.102 7.599 7000 7100 1.00 7.481 1.5 Pass <br /> Gallons=Cubic_Feet x 7.481 ISD_D fference —Gas_Flow_Meter_Di erence <br /> %Difference= g°!t°"S gallons X100 <br /> Gas_Flow_Meter_Di <br /> erencegall°ns <br /> I declare,under penalty ofperjury under the laws of the state of California that based on information and beliefformed after reasonable inquiry,the statements and information provided in this document are true, <br /> accurate,and complete. <br /> Signature of Technician: �— <br /> Ver. 1.0—09.18.08 <br />