Laserfiche WebLink
by R E C E INIFED <br /> AUG 103 91018 <br /> 0 <br /> ENVIROI`MENTP%L <br /> Line Leak Detector Test Data Sheet HEMI-TH nFPAR T�A.ENT <br /> Station # Arco 7148 Date 06/19/2018 20 <br /> Address 3400 N. MacArthur Dr. Tracy, CA 95376 <br /> Test Information <br /> 1 2 3 4 5 <br /> Product 87 91 D S L <br /> Manufacturer VP VP VP <br /> Model LD2000 LD2000 LD2000 <br /> Full Operating Pressure (psi) 32 32 32 <br /> Line Bleed Back(ml) 180 m l 180 m l 180 m l <br /> Trip Time (sec) 2 sec 3 sec 2 sec <br /> Metering Pressure (psi) 18 18 18 <br /> F/E Holding Pressure (psi) 30 30 30 <br /> Test Leak Rate (ml/min)(gph) 189 ml 189 ml 189 ml <br /> PASS or FAIL pass pass pass <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Gettler Ryan Inc <br /> Technician David Rouse//fLic#220793 <br /> Signature <br />