Up <br /> 44f <br /> Line Leak Detector Test Data Sheet <br /> Station # Arco 2186 Date 1 /3/2019 20 <br /> Address 3212 N California . Stockton , CA 95204 <br /> Test Information <br /> 1 2 3 4 5 <br /> Product 87 91 <br /> Manufacturer VR VR <br /> Model 848480 848480 <br /> Full Operating Pressure ( psi ) 36 36 <br /> Line Bleed Back ( ml ) NA NA <br /> Trip Time (sec ) NA NA <br /> Metering Pressure ( psi ) NA NA <br /> FIE }-folding Pressure ( psi ) 34 35 <br /> Test Leak [late ( ml /min ) ( gph ) 189ML 189ML <br /> PASS or FAIL pass pass <br /> i <br /> Comments : <br /> E <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct . The mechanical leak test detector test pass/ fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI . <br /> Inspected By * Contractor Gettler Ryan Inc <br /> Technician David Roue Lie# 220793 <br /> Signature <br /> i <br />